Module type
|
6 relay outputs normally open /normally closed
|
Module supply voltage
|
120 to 230 VAC
|
Module supply current consumption
|
125 mA at 120 VAC; 65 mA at 230 VAC
|
Power dissipation
|
15 W
|
I/O map
|
1 output word
|
Output to output
|
1780 VAC RMS for 1 minute
|
Field to logic
|
1780 VAC RMS for 1 minute
2500 VDC RMS for 1 minute
|
Field to Protective Earth
|
1780 VAC RMS for 1 minute
|
Field to communication adapter
|
Defined by communication adapter type
|
Internal
|
none
|
External: operating voltage (L+)
|
315 mA fast-blow (Wickman1930315000)
|
Immunity
|
IEC 1131-2
Surge on auxiliary power supply AC 2 KV to PE, 1 KV to differential surge on auxiliary power supply DC 0.5 KV.
|
Emissions
|
EN 50081-2
|
Agency approvals
|
UL, CSA, CE
FM Class 1 Div.2 pending
|
Width
|
125 mm (4.9 in)
|
Depth (with no adapter)
|
40 mm (1.54 in)
|
Length
|
141.5 mm (5.5 in) with or without one busbar
159.5mm (6.3 in) two busbars
171.5 mm (6.75 in) three busbars
|
Weight
|
260 g (0.57lb)
|
Output type
|
Form C relay, NO/NC contact
|
Relay contact material
|
Gold lash over silver alloy
|
Number of points
|
6
|
Number of groups
|
6
|
Points per group
|
1
|
Switched Output Voltage
|
|
AC
|
20-250 VAC
|
DC
|
30-150 VDC
|
Maximum Load Current
|
|
AC
|
5A @ 250 VAC @ 60 degrees C resistive load
2A Tungsten lamp load
3A @ power factor 0.4
|
DC
|
300mA resistive @ 60 degree C resistive load
100mA (L/R=10msec)
5A @ 5-30VDC @ 60 degrees C resistive load
|
Minimum Load Current
|
|
AC
|
0.5mA
|
DC
|
0.5mA
|
Maximum surge current
|
20A each point (cap. load @ 10 ms.)
|
Maximum switching capability
|
1250 VAC (resistive load)
|
Maximum module current
|
21A at 60 degrees C
25A at 30 degrees C
|
Output leakage current
|
< 100 microamps
|
Fault sensing
|
None
|
Fault reporting
|
None
|
Error indication
|
None
|
Response time
|
10 ms @ 60 Hz OFF to ON
20 ms @ 60 Hz ON to OFF
|
Maximum switching cycles
|
> 30 x 106 (mechanical)
>=1 x 105 (inductive load with external protective circuitry)
|