module type
|
16 discrete inputs in 1 group
16 discrete outputs in 1 group
|
supply voltage
|
10-60 VDC
|
supply voltage range
|
10-60 VDC
|
supply current consumption max
|
500 mA at 12 VDC
250 mA at 24 VDC
125 mA at 48 VDC
|
power dissipation
|
6 W + ( ( # of input points on x .144 W) + (# of output points on x .25 W) )
|
I/O map
|
1 input word or 16 discrete inputs
1 output word or 16 discrete outputs
|
input to input
|
none
|
output group to output group
|
none
|
input to output
|
707 VDC
|
logic to output
|
707 VDC
|
field to protective earth
|
707 VDC
|
input to output
|
707 VDC
|
field to communication adapter
|
defined by communication adapter type
|
internal
|
none
|
external: operating voltage (row 1)
|
1 A slow-blow
|
external: input reference voltage
(row 3)
|
1 A slow-blow (Bussmann GDC-1A or equivalent)
|
external: output voltage (row 2)
|
according to the supply of the connected actuators, not to exceed 8 A fast-blow.
|
immunity
|
IEC 1131-2
Surge on auxiliary power supply, 500V
|
emissions
|
EN 50081-2 (limitation A)
|
agency approvals
|
UL, CSA, CE, FM Class 1, Div. 2 pending
|
width
|
125 mm (4.9 in)
|
depth (with no adapter)
|
40 mm (1.54 in)
|
length
|
141.5 mm (5.5 in) with or without one busbar
159.5mm (6.3in) two busbars
171.5 mm (6.75in) three busbars
|
weight
|
200 g (0.44 lb)
|
number of points
|
16
|
number of groups
|
1
|
ooints per group
|
16
|
signal type
|
true high
|
IEC 1131 type
|
1+ (See Appendix for definitions of IEC input types.)
|
input voltage level
|
|
12 VDC +20%,-15%
24 VDC +25%,-20%
48 VDC +25%,-20%
|
>7.5 VDC On, <2.5 VDC Off
>11 VDC On, <5 VDC Off
>30 VDC On, <10 VDC Off
|
OFF state leakage current
|
|
12 VDC
24 VDC
48 VDC
|
1.5 mA and lower
1.5 mA and lower
1.5 mA and lower
|
input operating current
|
|
12 VDC ON current
24 VDC ON current
48 VDC ON current
|
2.3 mA
2.7 mA
2.9 mA
|
input voltage range
|
10-60 VDC
|
input voltage surge
|
75 volts peak for 10ms
|
response time
|
3.5 ms OFF to ON
5.5 ms ON to OFF
|
output type
|
solid state switch
|
output supply voltage
|
10-60 VDC
|
number of points
|
16
|
number of groups
|
1
|
current capacity
|
460 mA/point maximum up to 40 degrees C
430 mA/point from 40 degrees C to 50 degrees C
375 mA/point from 50 degrees C to 60 degrees C
|
signal type
|
true high (sourcing)
|
leakage current (output out)
|
< 1 mA @ 60 VDC
|
surge (inrush) current
|
5 A for 1 ms
|
on state voltage drop
|
< 1.0 VDC @ 0.5 A
|
fault sensing
(See Note below.)
|
Outputs are electronically safeguarded to assist in short circuit and overload protection.
|
fault reporting
|
1 red LED/point (row 3) ON when short current/ overload occurs
|
error indication
|
output overload for at least one output (I/O-error) to communication adapter
|
response time
(resistive load / 460 mA)
|
< 3 ms OFF to ON
< 3 ms ON to OFF
|
maximum switching cycles
|
1000/h for 0.5 A inductive load
100/s for 0.5 A resistive load
8/s for 1.2 W Tungsten load
|