Word
|
Function
|
---|---|
1
|
Status word (module status)
|
2
|
State of the eight discrete inputs
|
3
|
Analog input word channel 1
|
4
|
Analog input word channel 2
|
5
|
Analog input word channel 3
|
6
|
Analog input word channel 4
|
7
|
Analog input word channel 5
|
8
|
Analog input word channel 6
|
9 ... 12
|
Not used
|
Bits 15 ... 9
|
Bit 8
|
Bits 7 ... 4
|
Bit 3 (Channel 7, 8)
|
---|---|---|---|
Not used
|
0 = Bad module health
(module lost communication)
1 = Healthy module
|
Not used
|
0 = Fault 1 = No Fault
|
Bit 2 (Channel 5, 6)
|
Bit 1 (Channel 4, 3)
|
Bit 0 (Channel 1, 2)
|
---|---|---|
0 = Fault 1 = No fault
|
0 = Fault 1 = No fault
|
0 = Fault 1 = No fault
|
I/O Map Register
|
Data Type
|
---|---|
3x + 1
|
Data for discrete input
|
3x + 2
|
Data for analog input channel 1
|
3x + 3
|
Data for analog input channel 2
|
3x + 4
|
Data for analog input channel 3
|
3x + 5
|
Data for analog input channel 4
|
3x + 6
|
Data for analog input channel 5
|
3x + 7
|
Data for analog input channel 6
|
Input Voltage
|
Data is Left Justified
|
Comment
|
|
---|---|---|---|
Input Range
|
-10.000 ... +10.000
|
00382 ... 32382
|
Nominal input voltage range
|
Input Over Range
|
+10.000 ... +10.238
|
32384 ... 32764
|
Linear over range input voltage
|
Input Out of Range
|
≥10.238
|
32766 (7FFE Hex)
|
Input voltage exceeding threshold may damage the module.
|
Input Under Range
|
-10.238 ... -10.000
|
00002 ... 00382
|
Linear under voltage range
|
Input Out of Range
|
≤-10.238
|
00000
|
Input voltage exceeding threshold may damage the module.
|