1LED
2Address switch for the PROFIBUS DP address
LED
|
Status
|
Meaning
|
---|---|---|
BF
|
Red
|
Bus error:
The internal watchdog has responded or a reset has occurred.
|
Off
|
The module is working in a data exchange cycle.
|
PROFIBUS DP Address
|
Upper Address Switch (x 10)
|
Lower Address Switch (x 1)
|
---|---|---|
1 ... 9
|
0
|
1 ... 9
|
10 ... 19
|
1
|
0 ... 9
|
20 ... 29
|
2
|
0 ... 9
|
30 ... 39
|
3
|
0 ... 9
|
40 ... 49
|
4
|
0 ... 9
|
50 ... 59
|
5
|
0 ... 9
|
60 ... 69
|
6
|
0 ... 9
|
70 ... 79
|
7
|
0 ... 9
|
80 ... 89
|
8
|
0 ... 9
|
90 ... 99
|
9
|
0 ... 9
|
![]() |
Addressing on the PROFIBUS DP
Do not begin operating any module before the slave address has been set. See your network administrator to find out the correct device addresses.
Should you need to modify the addresses while the module is in operation, the power supply must be switched off and then on again. This is because addresses are only uploaded at the point when voltage is applied.
No duplicate addresses may be used with the PROFIBUS, because this can lead to conflicts on the bus.
Failure to follow these instructions can result in injury or equipment damage.
|
Terminal
|
Signal
|
Meaning
|
---|---|---|
3
|
RxD/TXD-P
|
Incoming data (RxD) positive,
Outgoing data (TxD) positive
|
5
|
DGND
|
Reference potential for terminations, only applies to connectors with termination (supplied by the I/O module)
|
6
|
VP
|
Supply voltage for terminations, only applies to connectors with termination (+5 V supplied by the I/O module)
|
8
|
RxD/TXD-N
|
Incoming data (RxD-N) negated,
Outgoing data (TxD-N) negated
|
1, 2, 4, 7, 9
|
Pin not connected
|
|
Connector housing
|
Cable shield connection (internally connected)
|