Safety CPU & Copro
The BME•58•040S CPU and the BMEP58CPROS3 Coprocessor (Copro) provide the following performance characteristics in a SIL3 M580 safety solution:
Performance Feature |
BME |
|||||||
---|---|---|---|---|---|---|---|---|
P582040S |
P584040S |
P586040S |
H582040S |
H584040S |
H586040S |
|||
Local racks |
4 (1 main rack + up to 3 extended racks) |
8 (1 main rack + up to 7 extended racks) |
8 (1 main rack + up to 7 extended racks) |
1 |
1 |
1 |
||
RIO drops (max of 2 racks/drop: main rack + extended rack) |
8 drops (up to 2 racks per drop) |
16 drops (up to 2 racks per drop) |
31 drops (up to 2 racks per drop) |
8 drops (up to 2 racks per drop) |
16 drops (up to 2 racks per drop) |
31 drops (up to 2 racks per drop) |
||
I/O Channels |
Discrete I/O |
2048 |
4096 |
6144 |
01 |
01 |
01 |
|
Analog I/O |
512 |
1024 |
1536 |
01 |
01 |
01 |
||
Expert |
72 |
144 |
216 |
01 |
01 |
01 |
||
Ethernet Ports |
Backplane |
1 |
1 |
1 |
1 |
1 |
1 |
|
Service |
1 |
1 |
1 |
1 |
1 |
1 |
||
RIO |
2 |
2 |
2 |
2 |
2 |
2 |
||
Control network |
Max # of modules/devices |
64 |
128 |
128 |
64 |
128 |
128 |
|
Max input capacity |
16 KB |
24 KB |
24 KB |
16 KB |
24 KB |
24 KB |
||
Max output capacity |
16 KB |
24 KB |
24 KB |
16 KB |
24 KB |
24 KB |
||
Max FAST input capacity |
3 KB |
5 KB |
5 KB |
3 KB |
5 KB |
5 KB |
||
Max FAST output capacity |
3 KB |
5 KB |
5 KB |
3 KB |
5 KB |
5 KB |
||
Distributed equipment network |
Max # of modules/devices |
61 |
61 |
61 |
61 |
61 |
61 |
|
Max input capacity |
2 KB |
8 KB |
8 KB |
2 KB |
2 KB |
2 KB |
||
Max output capacity |
2 KB |
8 KB |
8 KB |
2 KB |
2 KB |
2 KB |
||
Max CIP Safety devices |
16 |
64 |
128 |
– |
– |
– |
||
Max CIP Safety connections |
32 |
128 |
256 |
– |
– |
– |
||
Ethernet comm modules on local rack |
Max Eth Comm Modules |
2 |
4 |
4 |
2 |
4 |
4 |
|
Max BMENOC0301/0311 |
2 |
3 |
3 |
2 |
3 |
3 |
||
Max BMENOC0321 |
2 |
2 |
2 |
2 |
2 |
2 |
||
Memory allocation (max) |
Non-safe application program |
8 MB |
16 MB |
64 MB4 |
8 MB |
16 MB |
64 MB4 |
|
Safe application program |
2 MB |
4 MB |
16 MB4 |
2 MB |
4 MB |
16 MB4 |
||
Non-safe data |
768 KB |
2048 KB |
up to 65536 KB4 |
768 KB |
2048 KB |
up to 65536 KB4 |
||
Max configurable retained data |
768 KB |
2048 KB |
4096 KB |
768 KB |
2048 KB |
4096 KB |
||
Max configurable redundant transfer data |
– |
– |
– |
768 KB |
2048 KB |
4096 KB5 |
||
Safe data (non-retained data) |
512 KB |
1024 KB |
1024 KB4 |
512 KB |
1024 KB |
1024 KB4 |
||
Max configurable safe redundant transfer data |
– |
– |
– |
512 KB |
1024 KB |
1024 KB5 |
||
Shared: Global -> Safe |
16 KB |
16 KB |
16 KB |
16 KB2 |
16 KB2 |
16 KB2 |
||
Shared: Safe -> Global |
16 KB |
16 KB |
16 KB |
16 KB2 |
16 KB2 |
16 KB2 |
||
Shared: Global -> Process |
16 KB |
16 KB |
16 KB |
16 KB2 |
16 KB2 |
16 KB2 |
||
Shared: Process -> Global |
16 KB |
16 KB |
16 KB |
16 KB2 |
16 KB2 |
16 KB2 |
||
Total Data Storage |
4 GB6 |
4 GB6 |
4 GB6 |
4 GB6 |
4 GB6 |
4 GB6 |
||
Instruction execution rate |
MAST and FAST tasks: |
|||||||
Boolean |
10K instructions / ms |
40K instructions / ms |
60K instructions / ms |
10K instructions / ms |
40K instructions / ms |
60K instructions / ms |
||
Typed |
7.5K instructions / ms |
30K instructions / ms |
40K instructions / ms |
7.5K instructions / ms |
30K instructions / ms |
40K instructions / ms |
||
SAFE task: |
||||||||
Boolean |
10K instructions / ms |
40K instructions / ms |
40K instructions / ms |
10K instructions / ms3 |
40K instructions / ms3 |
40K instructions / ms3 |
||
Typed |
7.5K instructions / ms |
30K instructions / ms |
30K instructions / ms |
7.5K instructions / ms3 |
30K instructions / ms3 |
30K instructions / ms3 |
||
1. For M580 safety Hot Standby PACs, no I/O modules are supported in the local rack. 2. This data is included in both the safe and non-safe data areas. 3. Because the SAFE task exchanges data through backplane, there is a negative impact on performance. It takes 1ms to transfer 10KB for BMEH584040S and BMEH586040S and 2ms for BMEH582040S. 4. Application Program (non-safe) + Application Data (non-safe non-retain data only ) + Application Program (safe) + Application Data (Safe) is less than 64Mbytes. There is a global memory pool of 64 Mbytes on BME•586040S CPU for Application Program and Application Data. 5. Maximum of Transfer data (non safe + safe) for redundant data is 4MB. 6. 2 GB without an external memory card. |