Introduction
These tables describe the various causes for communication interruptions in complex M580 system architectures.
For the CPU with Ethernet I/O scanner service, refer to the Modicon M580 Hardware Reference Manual.
For the BM•CRA312•0 X80 EIO adapter modules, refer to the Modicon M580 Remote I/O Modules Installation and Configuration Guide.
For the BMENOC0301/11 Ethernet communication module, refer to the Modicon M580 BMENOC0301/11 Ethernet Communication Module Installation and Configuration Guide.
For the BMENOS0300 network option switch module, refer to the Modicon M580 BMEN0S0300 Network Option Switch Module Installation and Configuration Guide.
For the BMENOC0321 control network switch module, refer to the Modicon M580 BMENOC0321 Control Network Module Installation and Configuration Guide.
Ethernet Communication Modules in the Local Rack
Monitor diagnostics for Ethernet Communication Modules in the Local Rack:
Status of... |
Module [1] |
User Application [2] |
Control Expert [3] |
Rack Viewer [5] |
Ethernet Management Tool [6] |
---|---|---|---|---|---|
BMENOC0301/11 Ethernet backplane connection broken |
BMENOC0301/11 active LED |
||||
BMENOC0301/11 reset |
BMENOC0301/11 LED |
BMENOC0301/11 health bit (in CPU system word) I/O scanner connection status |
DTM online diagnostic inoperable |
yes |
yes |
BMENOC0301/11 inoperable |
BMENOC0301/11 LED |
BMENOC0301/11 health bit (in CPU system word) I/O scanner connection status |
DTM online diagnostic inoperable |
yes |
yes |
|
Ethernet RIO Network
NOTICE | |
---|---|
Monitor diagnostics for the Ethernet RIO network:
Status of... |
Module [1] |
User Application [2] |
Rack Viewer [5] |
Ethernet Management Tool [6] |
---|---|---|---|---|
duplicate IP address in CPU or BMXCRA312•0 |
BMEP58•0•0 LED BM•CRA312•0 LED |
|||
CPU (single) cable pulled out |
BMEP58•0•0 active LED |
CPU status byte CPU DDDT |
yes |
yes |
BM•CRA312•0 (single) cable pulled out |
BM•CRA312•0 ACT LED |
drop connection status (in CRA DDDT) |
yes |
|
BMENOS0300 diagnostic |
ACT LED |
web page |
yes |
|
DRS powered off |
DRS power LED |
DATA_EXCH block: monitor DRS (ports 5 and 6) |
yes |
|
DRS cable pulled out |
DRS ACT LED |
DATA_EXCH block: monitor DRS (ports 5 and 6) |
DRS web |
yes |
EIO system bit (part of CPU DDT) |
DRS web (only if cable on DRS port is broken) |
|||
DATA_EXCH block: monitor DRS (ports 5 and 6) |
DRS web |
|||
RIO traffic too slow (due to bad configuration or cabling) |
DATA_EXCH block: monitor DRS (port 5 and 6) Also possible via CRA DDDT |
|||
DIO traffic too slow (generate too much traffic) |
DATA_EXCH block: monitor DRS (port 5 and 6) |
DRS web |
MIB |
|
|
Ethernet RIO Drops
Monitor diagnostics for Ethernet RIO drops:
Status of... |
Module [1] |
User Application [2] |
Rack Viewer [5] |
ConneXium Network Manager [6] |
---|---|---|---|---|
BM•CRA312•0 powered off or disconnected |
BM•CRA312•0 LED |
drop connection status (in CPU DDDT) detected drop error status (in CPU DDDT) |
yes |
|
BM•CRA312•0 not configured |
BM•CRA312•0 LED CPU LED |
drop connection status (in CPU DDDT) detected drop error status (in CPU DDDT) |
yes (It does not appear on the screen.) |
|
extended rack inoperable (detected fault in BM• XBE 100 00 or cable) |
module PWR LED |
remote module health bits (in device DDDT) |
yes |
|
|
RIO Modules
Monitor diagnostics for RIO modules:
Status of... |
Module [1] |
User Application [2] |
Rack Viewer [5] |
---|---|---|---|
module absent, inoperable, or misplaced |
May be possible via LEDs |
remote module health bit (in CPU DDDT and in Device DDT (for Modicon X80 modules)) |
yes |
module status |
module LED (depends on module) |
module’s status byte |
yes |
|
Distributed Equipment
Monitor diagnostics for distributed equipment:
Status of... |
User Application [2] |
Rack Viewer [5] |
ConneXium Network Manager [6] |
---|---|---|---|
disconnected |
CPU connection status |
yes |
yes |
|