Visual Verification of DTM Configuration
Use the
tab for the CIP Safety DTM, created with or without a vendor EDS file, to compare the parameters defined in this DTM (and displayed in this tab) with the parameters set in to the device target DDDT. You can do this using an animation table in Control Expert, when Control Expert is operating in connected mode and is connected to the CPU.)NOTE: After an application download, you need to visually verify for each
CIP Safety target that all CIP safety configuration parameters downloaded
in the M580 originator for that target are identical to the ones configured
in the target DTM. You can do this by comparing configuration parameters
displayed in the CIP Safety target DDDT (using an animation table
with Control Expert in connected mode) with the ones configured in
the DTM and displayed in the Configuration verification tab.
Validating the Downloaded Configuration
After all CIP Safety configurations are download, user testing is the means by which all downloads are validated. One of the validation tests is to test the safety connection configurations after they are applied in an originator to confirm the target connection is operating as intended.