Introduction
The M580 safety power supply modules present two sets of derived data types (DDTs):
PWS_DIAG_DDT_V2 for diagnostics
PWS_CMD_DDT for commands
PWS_DIAG_DDT_V2
Byte Offset |
Name |
Type |
Comment |
---|---|---|---|
0 |
Reserved |
BYTE |
– |
1 |
Reserved |
BYTE |
– |
2 |
PwsMajorVersion |
BYTE |
Power supply Major firmware version |
3 |
PwsMinorVersion |
BYTE |
Power supply Minor firmware version |
4 |
Model |
BYTE |
Model identifier Model identifier:
|
5 |
State |
BYTE |
Power supply state |
6 |
I33BacPos |
UINT |
Measure current on 3.3V backplane line in nominal role (producer) |
8 |
V33Buck |
UINT |
Measure voltage of 3.3V Buck |
10 |
I24Bac |
UINT |
Measure current of 24V backplane line |
12 |
V24Int |
UINT |
Measure voltage of 24V Int |
14 |
Temperature |
INT |
Measure of Ambient Temperature |
16 |
OperTimeMasterSincePO |
UDINT |
Operating Time as Master since last Power ON |
20 |
OperTimeSlaveSincePO |
UDINT |
Operating Time as Slave since last Power ON |
24 |
OperTimeMaster |
UDINT |
Operating Time as Master since Manufacturing |
28 |
OperTimeSlave |
UDINT |
Operating Time as Slave Since Manufacturing |
32 |
Work |
UDINT |
Work supplied since Manufacturing |
36 |
RemainingLTPC |
UINT |
Remaining Life Time in percent |
38 |
NbPowerOn |
UINT |
Number of Power ON since Manufacturing |
40 |
NbVoltageLowFail |
UINT |
Number of failure detected on Primary Voltage by Low Threshold |
42 |
NbVoltageHighFail |
UINT |
Number of failure detected on Primary Voltage by High Threshold |
44 |
Reserved |
UDINT |
– |
48 |
Reserved |
UDINT |
– |
52 |
RemainingLTMO |
UINT |
Remaining Life Time in month |
54 |
Reserved |
BYTE |
– |
63 |
Reserved |
BYTE |
– |
PWS_CMD_DDT
Byte Offset |
Name |
Type |
Comment |
---|---|---|---|
0 |
Reserved |
BYTE |
– |
1 |
Code |
BYTE |
Command code:
|
2 |
PwsTarget |
BYTE |
Power supply target: 1 for left& 2 for right& 3 for both Power supply target:
|
3 |
Reserved |
BYTE |
– |
15 |
Reserved |
BYTE |
– |