Introduction
In the Control Expert dialog, you can:
define or verify address information about the adapter module (name, IP address, and subnetwork mask)
specify a hold-up time interval
specify I/O refresh rates
Access the Parameter Dialog
To access the Control Expert:
dialog inStep |
Action |
Comment |
---|---|---|
1 |
Expand (+) EIO Bus in the Control Expert . |
|
2 |
Double-click the installed adapter. |
The window appears. |
3 |
Select the tab. |
The dialog appears. |
Parameter Descriptions
parameters:
Parameter |
Comment |
---|---|
|
The name of the adapter module includes a fixed prefix and a number provided by the rotary switch. Valid names conform to this structure: BM•CRA_xxx, where xxx equals the 3-digit value selected on the rotary switch. When the adapter is placed in the remote drop, the number is set to the device number. The device number does not change if the device moves to a new location. Each adapter needs to be assigned a unique number within the application. A message like this appears when analysis reveals a duplicate number:
|
|
You cannot edit the IP address and sub network (mask) fields. NOTE: The IP
address is editable only in the tab of the CPU module. The value for sub network is deduced from the CPU sub-network
mask.
|
|
Edit the Control Expert:
inStep |
Action |
---|---|
1 |
In the X80 performance EIO adapter window, select the tab. |
2 |
Click the configuration hyperlink.NOTE: An table that lists all RIO drops
in the system appears.
|
3 |
Double-click the arrow in the RIO drop in the BME•58_ECPU_EXT column. column matching the desired |
4 |
Edit the in the field to reflect the new name |
5 |
Close the window and validate your project. |
Hold up time parameter:
Parameter |
Comment |
---|---|
|
The hold up time represents the time (ms) that device outputs are maintained in their current states after a communication disruption and before taking their fallback values:
|
If you assign a hold up time value that is less than the recommended minimum value, an I/O module may move to its fallback state. When communications are restored, the I/O module restarts and may not operate as anticipated.
There is only one hold up time for an RIO drop (not one for each task) based on the watchdog value.
One RPI per task = task period/2
WARNING | |
---|---|
:
Parameter |
Comment |
---|---|
|
Select this to configure the setting. |
|
Inputs: The RPI is the input refresh rate at which the adapter module sends inputs to the CPU with Ethernet I/O scanner service. The RPI is set in the subscribe field for the adapter on the remote I/O drop:
|
|
Outputs: Outputs are passed from the CPU with Ethernet I/O scanner service to the adapter. The default values are:
You cannot edit this value. The outputs are published synchronously or immediately at the end of the current MAST task. NOTE: The default value for the watchdog timer is 250 ms. If the MAST task
does not finish within the watchdog period, the process times out.
|
When the Periodic mode is selected for the MAST task, the Period value allows the complete execution of the logic. (The MAST can overrun when its execution time exceeds this value.) Valid values: 1...255 ms (increment: 1 ms).
When Cyclic mode is selected for the MAST task, the outputs are sent upon the completion of the task. The Watch Dog value (10 ... 1500 ms, increment: 10 ms, default = 250 ms) should be greater than the execution time.
LL984 Function Blocks
Quantum RIO drops that are used in a Modicon M580 system can use LL984 function blocks. For details, refer to Unity Pro Enhanced LL984 Block Library.