Access the Service Port Tab

The BM•CRA31210 adapter modules have a service port that can be configured for Ethernet communications or for port mirroring.

Double-click the adapter module in the Control Expert configuration to access the Service Port tab.

Service Port Parameters

These parameters are on the Control Expert Service Port tab:

Field

Parameter

Value

Comment

Service Port

Enabled

Enable port and edit port parameters.

Disabled

Disable port parameters.

Service Port Mode

Access (default)

This mode supports Ethernet communications.

Mirroring

In port mirroring mode, data traffic from one or more of the other ports is copied to this port. A connected tool can monitor and analyze port traffic.

NOTE: In this mode, the service port acts like a read-only port. That is, you cannot access devices (ping, connection to Control Expert, etc.) through the service port.
NOTE: This mode is not available on the BMXCRA31200.

Access Port Configuration

Service Port Number

ETH1

You cannot edit the value in the Service Port Number field.

Port Mirroring Configuration

Source Port(s)

Internal Port

Ethernet traffic through the internal port

ETH2

Ethernet traffic through the first RIO port

ETH3

Ethernet traffic through the second RIO port

Backplane Port

Ethernet traffic through the backplane port

Online Behavior

The Service Port parameters are stored in the application, however you can reconfigure (change) the parameters in the connected mode. Values that you reconfigure in the connected mode are sent to the remote drop adapter module or the CPU module in explicit messages. If the module does not respond to the explicit messages, a message appears.

NOTE: The changed values are not stored, so a mismatch can exist between the parameters that are being used and those that are in the stored application.
NOTE: The Service Port configuration can be read and modified online using the Service Port Control Object CIP object.