Introduction

The following I/O modules can be mounted in local racks or RIO drops in an M580 system.

Unless otherwise noted in the following tables, X80 I/O modules are supported on the following racks in RIO drops:

  • an X Bus rack with a BMXCRA312•0 X80 EIO adapter module

  • an Ethernet rack with a BMECRA312•0 eX80 EIO adapter module

Some of these modules also contain embedded web pages that can be used for configuration and diagnostics. Web page descriptions are provided in the appropriate product documentation and in Control Expert help.

NOTE: Conformally coated (hardened H) versions of many of these modules are also available. Refer to the specifications for hardened equipment in the Modicon M580, M340, and X80 I/O Platforms, Standards and Certifications guide.

Modicon X80 Analog Modules

Modules that require Ethernet across the backplane can be installed only in main local or remote local racks. They cannot be installed in extended racks.

NOTE: Debug screens are not available for analog modules in RIO drops and the parameters can’t be changed (Alignment, Filter, Offset...). If you need to modify the parameters, use the analog modules in local or local extended racks.

These analog I/O modules are supported in Modicon X80 local racks containing a CPU and RIO drops:

Type of Module

Module

Installation on...

Main Local Rack

Extended Local Rack

Main Remote Rack

Extended Remote Rack

input

BMXAMI••••

+(3)

+(3)

+

+

BMXART••••(1)

+(3)

+(3)

+

+

BMEAHI0812(2)

+(3)

-

+(4)

-

output

BMXAMO••••

+(3)

+(3)

+

+

BMEAHO0412(2)

+(3)

-

+(3)

-

input/output

BMXAMM0600

+(3)

+(3)

+

+

(1) The FAST task is not supported.

(2) These modules require an Ethernet backplane.

(3) Not supported in an M580 Hot Standby system.

(4) When installed in an RIO drop, use a BM•CRA31210 (e)X80 performance EIO adapter module. These modules are not compatible with BM•CRA31200 (e)X80 standard EIO adapter modules.

+ Allowed

- Not allowed

NOTE: A maximum of 2 analog modules are allowed on an RIO drop that contains a BMXCRA31200.2 X80 EIO adapter module. These analog modules can have a maximum of 8 channels (16 for analog I/O modules).

When the following modules are used in a local rack (containing a CPU) and RIO drops, they require these versions:

Module

Product Version

Software Version

BMXAMI0410

PV5

SV1.1

BMXAMM0600

PV5 or later

SV1.2

BMXAMO0210

PV7 or later

SV1.1

BMXART0414

PV5, PV6

SV2.0

PV7

SV2.1

BMXART0814

PV3, PV4

SV2.0

PV5 or later

SV2.1

NOTE: Schneider Electric recommends that you upgrade the modules with the latest available software version. (It is not necessary to update a BMXART0414 module, V2.1 or later, because it works correctly with a BM•CRA312•0 X80 EIO adapter module).

Modicon X80 Discrete Modules

NOTE: In the CPU configuration screen in Control Expert, you can configure a digital I/O module channel as a RUN/ STOP input by selecting this check box. This can be performed on a local I/O channel in topological I/O data type only. (This configuration is not available in Hot Standby systems).

These discrete I/O modules are supported in Modicon X80 local racks containing a CPU and RIO drops:

Type of Module

Module

Installation on...

Main Local Rack

Extended Local Rack

Main Remote Rack

Extended Remote Rack

input

BMXDAI••••

+(2)

+(2)

+

+

BMXDDI••••(1)

+(2)

+(2)

+

+

output

BMXDAO••••

+(2)

+(2)

+

+

BMXDDO••••

+(2)

+(2)

+

+

BMXDRA••••(1)

+(2)

+(2)

+

+

BMXDRC••••

+(2)

+(2)

+

+

input/output

BMXDDM••••

+(2)

+(2)

+

+

(1) Before installation of I/O modules that use a 125 Vdc power supply, refer to the temperature derating information in I/O module hardware guides for your platform.

(2) Not supported in an M580 Hot Standby system.

+ Allowed

- Not allowed

NOTE: Schneider Electric recommends that you upgrade the modules with the latest available software version. (It is not necessary to update a BMXART0414 module, V2.1 or later, because it works correctly with a BM•CRA312•0 X80 EIO adapter module.)

Communication Modules

These communication modules are supported in M580 local racks (containing a CPU with Ethernet I/O communication server service) and RIO drops that contain a BM•CRA312•0 X80 EIO adapter module:

Module

Comment

Installation on...

Main Local Rack

Extended Local Rack

Main Remote Rack

Extended Remote Rack

BMXNOM0200(1)

Only MAST task is supported.

Additional restrictions are described in chapter BMXNOM0200 Limitation and Implementation Rules.

Refer to the instruction to configure the BMXNOM0200 module in an X80 RIO drop

+(3)

+(3)

+(4)

+

BMXNOR0200

Only MAST task is supported.

+(3)

+(3)

-

-

BMXNGD0100

Dedicated to global data.

For configuration details, refer to the BMXNOE0100 user guide (3100713•). The BMXNGD0100 module has the same global data functionality as the BMXNOE0100, but it does not support these services: I/O scanning, address server, time synchronization, bandwidth monitoring, or web pages.

+(3)

-

-

-

BMXEIA0100(1)

Only MAST task is supported.

A maximum of 16 AS-i modules in an M580 configuration is allowed.

A maximum of two AS-i modules on an RIO drop containing a BM•CRA3•• X80 EIO adapter is allowed.

The following maximum number of AS-i modules on a local rack containing one of the following CPUs is allowed.

  • BMEP581020: two

  • BMEP582020: four

  • BMEP582040: four

  • BMEP583020: six

  • BMEP583040: six

  • BMEP584020: eight

  • BMEP584040: eight

  • BMEP585040: eight

  • BMEP586040: eight

A maximum of 16 AS-i modules is allowed in RIO drops in an M580 system that uses BME•585040 or BME•586040 CPUs.

+(3)

+(3)

+(4)

+

BMECXM0100(2)

Connects an M580 CPU on an Ethernet network to CANopen fieldbus devices.

Requires an Ethernet backplane.

+(3)

-

+

-

BMXNRP0200, BMXNRP0201

Fiber cable conversion

+

+

+

+

(1) If a BMXNOM0200 module and a BMXEIA0100 module are included on the same RIO drop, only one BMXNOM0200 module and two BMXEIA0100 modules maximum are allowed.

(2) Compatible with M580 CPUs V2.00 or later only.

(3) Not supported in an M580 Hot Standby system.

(4) When installed in an RIO drop, use a BM•CRA31210 (e)X80 performance EIO adapter module. These modules are not compatible with BM•CRA31200 (e)X80 standard EIO adapter modules.

+ Allowed

- Not allowed

Counting Modules

NOTE: When installed in an RIO drop, use a BM•CRA31210 (e)X80 performance EIO adapter module. These modules are not compatible with BM•CRA31200 (e)X80 standard EIO adapter modules.
NOTE: I/O event tasks are supported only through topological data type, not through device DDT.

These counting modules are supported in M580 local racks (containing a CPU with Ethernet I/O communication server service) and RIO drops that contain a BM•CRA31210 (e)X80 EIO performance adapter module:

Module

Comment

Installation on...

Main Local Rack

Extended Local Rack

Main Remote Rack

Extended Remote Rack

BMXEHC0200

 

+(1)

+(1)

+

+

BMXEHC0800

When configuring a BMXEHC0800 module, the dual phase counting mode function is not available in X80 EIO drops or when using device DDT in local racks.

When configuring a BMXEHC0800.2 module the dual phase counting mode function is available in X80 EIO drops and when using device DDT in local racks. In this case the event feature is not available.

+(1)

+(1)

+

+

BMXEAE0300

In RIO drops:

  • Events are not supported.

    If events are needed, move the module to the local rack.

  • A maximum of 36 channels can be configured.

+(1)

+(1)

+

+

(1) Not supported in an M580 Hot Standby system.

+ Allowed

- Not allowed

When the following modules are used in a local rack (containing a CPU) and RIO drops, they require these versions:

Module

Product Version

Software Version

BMXEHC0200

PV3

SV1.1

BMXEHC0800

PV3

SV1.1

NOTE: Schneider Electric recommends that you upgrade the modules with the latest available software version.

Intelligent and Special Purpose Modules

These intelligent/special purpose modules are supported in M580 local racks (containing a CPU with Ethernet I/O communication server service) and RIO drops that contain a BM•CRA312•0 X80 EIO adapter module:

Module

Comment

Installation on...

Main Local Rack

Extended Local Rack

Main Remote Rack

Extended Remote Rack

BMXERT1604T

Limitations for the time stamping module are described in chapter Compatibility and Limitations.

+(2)

+(2)

+(3)

+

PMXNOW0300

wireless multi-function access point/bridge

+(2)

+(2)

+

+

PMXCDA0400

diagnostic (machines, processes, and infrastructures)

+(2)

+(2)

+

+

PMESWT0100(1)

This is an Ethernet weighing transmitter (1 channel) and requires an Ethernet backplane.

+(2)

-

+

-

PMEUCM0302

universal communication

This requires an Ethernet backplane.

+(2)

-

+

-

PMEPXM0100

Profibus DP/DPV1 master module that requires an Ethernet backplane

+(4)

+(4)

+(5)

+(5)

BMENOR2200H

Modicon M580 BMENOR2200H Advanced RTU Module

       

BMENUA0100

Ethernet communication module with embedded OPC UA server

+

-

-

-

(1) Scanned as a device by the DIO scanner in the CPU.

(2) Not supported in an M580 Hot Standby system.

(3) When installed in an RIO drop, use a BM•CRA31210 (e)X80 performance EIO adapter module. These modules are not compatible with BM•CRA31200 (e)X80 standard EIO adapter modules.

(4) Not supported on a local rack in an M580 standalone system.

(5) Not supported on an EIO remote drop in an M580 Hot Standby system.

+ Allowed

- Not allowed