Introduction
The following I/O modules can be mounted in local racks or RIO drops in an M580 system.
Unless otherwise noted in the following tables, X80 I/O modules are supported on the following racks in RIO drops:
an X Bus rack with a BMXCRA312•0 X80 EIO adapter module
an Ethernet rack with a BMECRA312•0 eX80 EIO adapter module
Some of these modules also contain embedded web pages that can be used for configuration and diagnostics. Web page descriptions are provided in the appropriate product documentation and in Control Expert help.
Modicon X80 Analog Modules
Modules that require Ethernet across the backplane can be installed only in main local or remote local racks. They cannot be installed in extended racks.
These analog I/O modules are supported in Modicon X80 local racks containing a CPU and RIO drops:
Type of Module |
Module |
Installation on... |
|||
---|---|---|---|---|---|
Main Local Rack |
Extended Local Rack |
Main Remote Rack |
Extended Remote Rack |
||
input |
BMXAMI•••• |
+(3) |
+(3) |
+ |
+ |
BMXART••••(1) |
+(3) |
+(3) |
+ |
+ |
|
BMEAHI0812(2) |
+(3) |
- |
+(4) |
- |
|
output |
BMXAMO•••• |
+(3) |
+(3) |
+ |
+ |
BMEAHO0412(2) |
+(3) |
- |
+(3) |
- |
|
input/output |
BMXAMM0600 |
+(3) |
+(3) |
+ |
+ |
(1) The FAST task is not supported. (2) These modules require an Ethernet backplane. (3) Not supported in an M580 Hot Standby system. (4) When installed in an RIO drop, use a BM•CRA31210 (e)X80 performance EIO adapter module. These modules are not compatible with BM•CRA31200 (e)X80 standard EIO adapter modules. + Allowed - Not allowed |
When the following modules are used in a local rack (containing a CPU) and RIO drops, they require these versions:
Module |
Product Version |
Software Version |
---|---|---|
BMXAMI0410 |
PV5 |
SV1.1 |
BMXAMM0600 |
PV5 or later |
SV1.2 |
BMXAMO0210 |
PV7 or later |
SV1.1 |
BMXART0414 |
PV5, PV6 |
SV2.0 |
PV7 |
SV2.1 |
|
BMXART0814 |
PV3, PV4 |
SV2.0 |
PV5 or later |
SV2.1 |
Modicon X80 Discrete Modules
These discrete I/O modules are supported in Modicon X80 local racks containing a CPU and RIO drops:
Type of Module |
Module |
Installation on... |
|||
---|---|---|---|---|---|
Main Local Rack |
Extended Local Rack |
Main Remote Rack |
Extended Remote Rack |
||
input |
BMXDAI•••• |
+(2) |
+(2) |
+ |
+ |
BMXDDI••••(1) |
+(2) |
+(2) |
+ |
+ |
|
output |
BMXDAO•••• |
+(2) |
+(2) |
+ |
+ |
BMXDDO•••• |
+(2) |
+(2) |
+ |
+ |
|
BMXDRA••••(1) |
+(2) |
+(2) |
+ |
+ |
|
BMXDRC•••• |
+(2) |
+(2) |
+ |
+ |
|
input/output |
BMXDDM•••• |
+(2) |
+(2) |
+ |
+ |
(1) Before installation of I/O modules that use a 125 Vdc power supply, refer to the temperature derating information in I/O module hardware guides for your platform. (2) Not supported in an M580 Hot Standby system. + Allowed - Not allowed |
Communication Modules
These communication modules are supported in M580 local racks (containing a CPU with Ethernet I/O communication server service) and RIO drops that contain a BM•CRA312•0 X80 EIO adapter module:
Module |
Comment |
Installation on... |
|||
---|---|---|---|---|---|
Main Local Rack | Extended Local Rack | Main Remote Rack | Extended Remote Rack | ||
BMXNOM0200(1) |
Only MAST task is supported. Additional restrictions are described in chapter BMXNOM0200 Limitation and Implementation Rules. Refer to the instruction to configure the BMXNOM0200 module in an X80 RIO drop |
+(3) |
+(3) |
+(4) |
+ |
BMXNOR0200 |
Only MAST task is supported. |
+(3) |
+(3) |
- |
- |
BMXNGD0100 |
Dedicated to global data. For configuration details, refer to the BMXNOE0100 user guide (3100713•). The BMXNGD0100 module has the same global data functionality as the BMXNOE0100, but it does not support these services: I/O scanning, address server, time synchronization, bandwidth monitoring, or web pages. |
+(3) |
- |
- |
- |
BMXEIA0100(1) |
Only MAST task is supported. A maximum of 16 AS-i modules in an M580 configuration is allowed. A maximum of two AS-i modules on an RIO drop containing a BM•CRA3•• X80 EIO adapter is allowed. The following maximum number of AS-i modules on a local rack containing one of the following CPUs is allowed.
A maximum of 16 AS-i modules is allowed in RIO drops in an M580 system that uses BME•585040 or BME•586040 CPUs. |
+(3) |
+(3) |
+(4) |
+ |
BMECXM0100(2) |
Connects an M580 CPU on an Ethernet network to CANopen fieldbus devices. Requires an Ethernet backplane. |
+(3) |
- |
+ |
- |
BMXNRP0200, BMXNRP0201 |
Fiber cable conversion |
+ |
+ |
+ |
+ |
(1) If a BMXNOM0200 module and a BMXEIA0100 module are included on the same RIO drop, only one BMXNOM0200 module and two BMXEIA0100 modules maximum are allowed. (2) Compatible with M580 CPUs V2.00 or later only. (3) Not supported in an M580 Hot Standby system. (4) When installed in an RIO drop, use a BM•CRA31210 (e)X80 performance EIO adapter module. These modules are not compatible with BM•CRA31200 (e)X80 standard EIO adapter modules. + Allowed - Not allowed |
Counting Modules
These counting modules are supported in M580 local racks (containing a CPU with Ethernet I/O communication server service) and RIO drops that contain a BM•CRA31210 (e)X80 EIO performance adapter module:
Module |
Comment |
Installation on... |
|||
---|---|---|---|---|---|
Main Local Rack | Extended Local Rack | Main Remote Rack | Extended Remote Rack | ||
BMXEHC0200 |
+(1) |
+(1) |
+ |
+ |
|
BMXEHC0800 |
When configuring a BMXEHC0800 module, the dual phase counting mode function is not available in X80 EIO drops or when using device DDT in local racks. When configuring a BMXEHC0800.2 module the dual phase counting mode function is available in X80 EIO drops and when using device DDT in local racks. In this case the event feature is not available. |
+(1) |
+(1) |
+ |
+ |
BMXEAE0300 |
In RIO drops:
|
+(1) |
+(1) |
+ |
+ |
(1) Not supported in an M580 Hot Standby system. + Allowed - Not allowed |
When the following modules are used in a local rack (containing a CPU) and RIO drops, they require these versions:
Module |
Product Version |
Software Version |
---|---|---|
BMXEHC0200 |
PV3 |
SV1.1 |
BMXEHC0800 |
PV3 |
SV1.1 |
Intelligent and Special Purpose Modules
These intelligent/special purpose modules are supported in M580 local racks (containing a CPU with Ethernet I/O communication server service) and RIO drops that contain a BM•CRA312•0 X80 EIO adapter module:
Module |
Comment |
Installation on... |
|||
---|---|---|---|---|---|
Main Local Rack | Extended Local Rack | Main Remote Rack | Extended Remote Rack | ||
BMXERT1604T |
Limitations for the time stamping module are described in chapter Compatibility and Limitations. |
+(2) |
+(2) |
+(3) |
+ |
PMXNOW0300 |
wireless multi-function access point/bridge |
+(2) |
+(2) |
+ |
+ |
PMXCDA0400 |
diagnostic (machines, processes, and infrastructures) |
+(2) |
+(2) |
+ |
+ |
PMESWT0100(1) |
This is an Ethernet weighing transmitter (1 channel) and requires an Ethernet backplane. |
+(2) |
- |
+ |
- |
PMEUCM0302 |
universal communication This requires an Ethernet backplane. |
+(2) |
- |
+ |
- |
PMEPXM0100 |
Profibus DP/DPV1 master module that requires an Ethernet backplane |
+(4) |
+(4) |
+(5) |
+(5) |
BMENOR2200H |
Modicon M580 BMENOR2200H Advanced RTU Module |
||||
BMENUA0100 |
Ethernet communication module with embedded OPC UA server |
+ |
- |
- |
- |
(1) Scanned as a device by the DIO scanner in the CPU. (2) Not supported in an M580 Hot Standby system. (3) When installed in an RIO drop, use a BM•CRA31210 (e)X80 performance EIO adapter module. These modules are not compatible with BM•CRA31200 (e)X80 standard EIO adapter modules. (4) Not supported on a local rack in an M580 standalone system. (5) Not supported on an EIO remote drop in an M580 Hot Standby system. + Allowed - Not allowed |