Step
|
Action
|
---|---|
1
|
In Control Expert, open the DTM Browser (Tools → DTM Browser).
|
2
|
Right-click the CPU in the DTM Browser.
|
3
|
Select Connect.
|
4
|
Right-click the CPU in the DTM Browser.
|
5
|
Select Device menu → Diagnosis.
|
6
|
Click the Hot Standby Synchronization tab.
|
Parameter
|
Description
|
---|---|
Refresh Every 500ms
|
Select this to display synchronization data in this page, and refresh displayed data every 500ms.
|
Status area:
|
|
Synchronizing
|
|
Synchronized
|
|
Error Status
|
|
Manual Synchronization → Stop Synchronization area:
|
|
Stop Synchronization Service
|
Select this then click Send to stop the synchronization service.
NOTE: To re-start the synchronization service, select one of the Force Manual Synchronization options (below), then click Send. |
Manual Synchronization → Force Manual Synchronization area:
|
|
Copy Files from Standby to Primary
|
Select this then click Send to push DIO device configuration (.prm) files from the standby CPU to the primary.
|
Copy Files from Primary to Standby
|
Select this then click Send to pull DIO device configuration (.prm) files from the primary CPU to the standby.
|
Clear Files in Primary
|
Select this then click Send to delete the DIO device configuration (.prm) files from the primary. If synchronization is enabled, the standby CPU synchronizes with the primary and any DIO device configuration files in the standby are also deleted.
|