NOTICE
|
EQUIPMENT DAMAGE
During the transfer of the firmware file:
Failure to follow these instructions can result in equipment damage.
|
Step
|
Action
|
---|---|
1
|
Install on your PC the Unity Loader software.
|
2
|
Connect the PC that is running Unity Loader to one of the following ports on the standby CPU module:
|
3
|
Launch Unity Loader.
|
4
|
Click Firmware tab.
|
5
|
In the PC list box, select the .ldx file that contains the firmware file.
|
6
|
Check that transfer sign is green to allow transfer from PC to the module.
|
7
|
Click Transfer.
|
8
|
After the transfer of firmware is complete, click Close.
NOTE: Upon completion of the firmware update, the standby CPU remains the standby CPU. |
9
|
Confirm that the installation of firmware did not create an application mismatch condition.
|
10
|
Repeat steps 2 through 8, above, for the primary CPU.
NOTE:
|
Step
|
Action
|
---|---|
1
|
Install Unity Loader software.
|
2
|
Connect the PC that is running Unity Loader to the service port of the target module, which can be:
|
3
|
Launch Unity Loader.
|
4
|
Click Firmware tab.
|
5
|
In the PC list box, select the .ldx file that contains the firmware file.
|
6
|
Check that transfer sign is green to allow transfer from PC to the module.
|
7
|
Click Transfer.
|
8
|
Click Close.
|