Memory Consumption
Input and output memory specification for I/O data:
Scope
Type
Maximum Value per Scan1
BMEH582040(S)
BMEH584040(S)
BMEH586040(S)
M580 Hot Standby CPU
input bytes per network
16384 bytes2
24576 bytes3
24576 bytes 3
output bytes per network
16384 bytes2
24576 bytes3
24576 bytes 3
Ethernet RIO
input words per drop
1400
output words per drop
1400
Ethernet DIO
input bytes per device
up to 1400, depending on EtherNet/IP or Modbus/TCP function code
output bytes per device
1400
Total DIO scanning capability
input (KB)
up to 2
output (KB)
up to 2
1. Hot Standby supports the MAST, FAST, and SAFE tasks. AUX0 and AUX1 are not supported.
2. Of the total amount, up to 3072 bytes can be FAST task data.
3. Of the total amount, up to 5120 bytes can be FAST task data.
Displaying I/O Memory Consumption
You can monitor the I/O memory consumption in Control Expert. Use one of these methods:
Exceeding RIO Drop Limitations
Control Expert detects an error and displays it in the log if one of these events occurs:
Minimum / Maximum System Channels
The minimum and maximum number of channels that a global M580 configuration can manage is a function of the M580 CPU model that you are using. For detailed information on configuring channels, refer to the Modicon M580 Hardware Reference Manual.