System Performance
Original instructions
Memory Consumption
Input and output memory specification:
Scope
Type
Maximum Value per Task*
M580 CPU
input bytes per device
up to 32,768, depending on CPU model
output bytes per device
up to 24,576, depending on CPU model
Ethernet RIO
input words per drop
1400
output words per drop
1400
Ethernet DIO
input bytes per device
up to 1,400, depending on EtherNet/IP or Modbus/Modbus function code.
output bytes per device
1,400
Total DIO scanning capability
input Kbytes
up to 4, depending on CPU model
output Kbytes
up to 4, depending on CPU model
* You can use all four tasks (MAST, FAST, AUX0, AUX1) simultaneously.
Displaying I/O Memory Consumption
You can monitor the I/O memory consumption in Control Expert . Use one of these methods:
Exceeding RIO Drop Limitations
Control Expert displays an error in the log window if one of these events occurs:
Minimum / Maximum System Channels
The minimum and maximum number of channels that an M580 configuration can manage is a function of the Modicon M580 CPU model that you are using. For detailed information on configuring channels, refer to the M580 Hardware Reference Manual.