Installation Parts List—800 Series I/O Modules with Control Expert
(Original Document)
Manufacturers Part Numbers/Instructions
Callout
Vendor
Part Number
Description
Instructions
1
Schaffner
FN670-3/06
Line Filter (Fast on terminals)
Dimensions:
Length: 3.4 in (85 mm)
Width: 2.2 in (55 mm)
Height: 1.6 in (40 mm)
Mounting Holes:
0.2 in (5.3 mm) dia.
3 in (75 mm) centerline mounted
Fast on Terminals:
0.25 in (6.4 mm)
Install next to the 984 CPU.
2
Schneider
CER001 or equivalent
Grounding Bar
All cable shields must be grounded. NOTE: Not required if using steel conduit.
3
Flat Ground Braided Cable
4
Oflex
35005
3 conductor
100cy Series
Shielded Cable
maximum length: 30 in (760 mm)
The shield is terminated at the EMI Line Filter and open at CPU end. The third conductor is not used.
5
Oflex
35005
3 conductor
100cy Series
Shielded Cable
Terminate the shield at panel ground, at EMI Filter.