Requirement for
|
Description
|
---|---|
Power supply and I/O lines
|
All wiring for power supply and I/O lines must be in grounded steel conduits (EMT) or must use braided shielded cable.
If shielded cable is used, the braid must have 80% or more shield coverage, and the outside diameter of the braid (without jacket) must be in the range of 0.189 ... 0.237 in (4.8 ... 6.0 mm).
|
Cable shields
|
All cable shields must be grounded, using clips on the Grounding Bar (part number CER001).
Shield is not terminated at module field connector.
|
Grounding
|
Install braided earth ground to both
|
Line filters
|
Use a 110/220 Vac Line Filter (Schaffner part number FN670-30/6). Install as shown in the AC power input figure.
|