Description
|
Analog input
4 - 20 mA, 1 - 5 Vdc
|
Number of Channels
|
4, (B873-002)
8, (B875-002)
|
Operating Range
Voltage/Current
|
1 - 5 Vdc / 4 - 20 mA
|
Impedance
Voltage
Current
|
0.5 MΩ per input
1 MΩ differentially
|
Resolution
|
12 bit
|
Filter
|
-3 dB @ 18 Hz
Rolloff -20 dB per decade
|
Linearity
|
+.05% of full scale @ 25 °C (77 °F)
|
Protection
|
240 Vac RMS
|
Common Mode
Range
Rejection
|
0 Vac to 30 Vac RMS
> -86 dB @ 60 Hz
|
Isolation
Channel to Channel
Input to Case
Module
|
250 Vac RMS
500 Vac RMS for one minute
1500 Vac RMS for one minute
300 Vac RMS continuous
|
Accuracy
Overall
At 25 °C (77 °F)
Offset Drift
Gain Drift
|
7 mV or 19.7 μA
+/-0.488 mV or +/-1.95 μA @ 1.2207 mV
+/-30 μV or +/-0.12 μA per °C
+/-16.7 μV or +/-0.07 μA per °F
+/-15 ppm per °C
|
Repeatability
|
Over a twenty-four hour period, with a constant voltage and at a constant operating temperature, the input data value will be within +/-2 counts.
|
Power Required
+5 V
+4.3 V
-5 V
|
300 mA
300 mA
0 mA
|
Data Format
0000
4095
0000 to 4095
4096 to 8191
4096
8192
|
Power Up
On diagnostic failure or during failure recovery
Under range - standard
Under range - elevated
Valid - standard range
Valid - elevated range
Over range - standard
Over range - elevated
|
Throughput Rates
Update Interval
Out of Range
Terminal Connector
|
4 channels 400 ms
8 channels 710 ms
(Including diagnostics)
220 ms for each channel in under or over range condition (Refer to throughput section)
AS-8533-001 (B873-002)
AS-8533-002 (B875-002)
|
Reference Type
|
B873-002 Mapped as 4 registers input 3x
B875-002 Mapped as 8 registers input 3x
|
Input Type
|
BIN/BCD
|