The B808–016 230 Vac output module converts logic signals used within the PLC into 16 independent 230 Vac outputs. Each output is capable of driving a relay, pilot lamp, motor starter, solenoid, or any other load up to 2.0 A. The B808 is capable of 6 A per group of eight and handling 12 A per module.
The module uses triac switches to control loads connected to an external power source. These switches are designed to withstand the high surge currents typical of industrial loads.
Following is a simplified schematic of the B808–016 230 Vac output module.