Description
|
24 Vdc input
|
|
Number of Points
|
32
|
|
Number of Groups
|
4
|
|
Inputs/group
|
8
|
|
Working Voltage
|
0-30 Vdc
|
|
Reference Voltage
|
19.2-30 Vdc
|
|
Reference Current
|
9-15 mA/group
|
|
Threshold Voltage
|
11-15 Vdc
|
|
External Resistor
|
(Broken wire detect) 6.2 kΩ +10%, 1 external resistor/input point, resistor across contactor for nominally operated 24 Vdc system
|
|
Input Current
|
Low State
|
1.8- 3 mA
|
|
High State
|
5.75-7.1 mA
|
Transition Time
|
ON
|
V in = 20 Vdc: 200 ms minimum
|
|
V in = 30 Vdc: 25 ms minimum
|
|
|
OFF
|
V in = 20 Vdc: 100 ms maximum
|
V in = 30 Vdc: 250 ms maximum
|
||
Maximum Response Time
|
OFF→ ON
|
2 ms, contact opening or closing, 100 ms maximum fault detection time
|
ON →OFF
|
||
Power Required
|
+5 V
|
350 mA
|
+4.3 V
|
10 mA
|
|
-5 V
|
0 mA (not used)
|
|
Terminal Connector
|
AS-8535-000
|
|
Reference Type
|
Mapped as 64 bits input
1x
or
Mapped as 4 registers input
3x
|
|
Input Type
|
BIN/BCD
|