Addressing
(Original Document)
Flat Addressing
This module requires either 16 contiguous %I references or one %IW word. For a description of how to access the input points, please refer to Discrete I/O Bit Numbering.
Topological Addressing
The following tables show the topological addresses for the 140HLI34000 module.
Topological addresses in Bit Mapping format:
Point
I/O Object
Comment
Input 1
%I[\b.e\]r.m.1
Value
Input 2
%I[\b.e\]r.m.2
Value
• • •
Input 15
%I[\b.e\]r.m.15
Value
Input 16
%I[\b.e\]r.m.16
Value
Topological addresses in Word Mapping format:
Point
I/O Object
Comment
Inputword 1
%IW[\b.e\]r.m.1.1
Value
Used abbreviations: b = bus, e = equipment (drop), r = rack, m = module slot.
I/O Map Status Byte
There is no I/O map status byte associated with this module.