Diagnostic IDs
Original instructions
Diagnostic ID Definitions
Diagnostic IDs (TextIds) define the warning messages written in the diagnostic buffer.
Diagnostic ID
Warning message
CPU LED display message
13000
Default message
Power up
Diagnostic IDs for switching from Primary CPU to Offline:
Diagnostic ID
Warning message
CPU LED display message
13001
System halt
halt
13002
S908 Remote I/O inoperative
s908 fails
13003
ETH device error
hsby fails
13004
ETH communication problem
hsby fails
13005
Stop PLC command
stop
13006
Offline keypad switch
off keypad
13007
Offline Command register request
off %sw60
13032
Ethernet IO inoperative
eio fails
13033
S908 Remote CPR inoperative
s908 crp
13034
Ethernet Remote CPR inoperative
eio crp
Diagnostic IDs for switching from Standby CPU to Offline:
Diagnostic IDs
Warning message
CPU LED display message
13008
System halt
halt
13009
Remote I/O error
rio fails
13010
ETH device error
hsby fails
13011
ETH communication problem
hsby fails
13012
Stop PLC command
stop
13013
Offline keypad switch
off keypad
13014
Offline Command register request
eio fails
13027
Ethernet IO inoperative
eio fails
13028
S908 Remote CPR inoperative
s908 crp
13029
Ethernet Remote CPR inoperative
eio crp
Diagnostic IDs for switching from Standby CPU to Primary CPU:
Diagnostic ID
Warning message
CPU LED display message
13015
Control command over ETH
take over
13016
Control command over S908 RIO
take over
13030
Control command over Ethernet IO
take over
13031
Primary has disappeared, detected on 2 links
take over
Diagnostic IDs for switching from Offline to Primary CPU/Standby CPU:
Diagnostic ID
Warning message
CPU LED display message
13017
Switch from Offline to Primary CPU
run
13018
Switch from Offline to Standby CPU
plug&run
Diagnostic IDs for switching to Offline:
Diagnostic ID
Warning message
CPU LED display message
13019
Offline due to application mismatch
off appli
13020
Offline due to OS version mismatch
off vers
13021
Offline due to S908 RIO inoperative
off rio
13024
Offline due to command register
off %sw60
13025
Offline due to Ethernet IO inoperative
eio fails
13026
Offline due to Copro inoperative
copro fail
Other Diagnostic IDs:
Diagnostic ID
Warning message
CPU LED display message
13022
S908 CPR switches to kernel mode
crp fault
13023
Copro OS version not compatible
copro err