Exclusive Use of MAST Tasks
Timer Events and I/O Errors
Timer events are NOT synchronized in Quantum Hot Standby applications. Schneider Electric recommends not using timer events.
NOTE: If timer events are used, the detected I/O errors are not exchanged between Primary CPU and Standby CPU.
Mast Task Cycle Time and Watchdog
The Quantum Hot Standby system is optimized for applications with MAST task cycle times between, for a:
-
S908 system, 30 ms and 250 ms
-
Quantum Ethernet I/O system, 30 ms and 350 ms