MOD_FLT Byte Description
Original instructions
MOD_FLT Byte in Device DDT
MOD_FLT byte structure:
Bit
Symbol
Description
0
MOD_FAIL
  • 1: Internal detected error or module failure detected.
  • 0: No detected error
1
CH_FLT
  • 1: Inoperative channels.
  • 0: Channels are operative.
2
BLK
  • 1: Terminal block detected error.
  • 0: No detected error.
NOTE: This bit may not be managed.
3
  • 1: Module in self-test.
  • 0: Module not in self-test.
NOTE: This bit may not be managed.
4
Not used.
5
CONF_FLT
  • 1: Hardware or software configuration detected error.
  • 0: No detected error.
6
NO_MOD
  • 1: Module is missing or inoperative.
  • 0: Module is operating.
NOTE: This bit is managed only by modules located in a remote rack with a BME CRA 312 10 adapter module. Modules located in the local rack do not manage this bit that remains at 0.
7
Not used.