If you edited a HART Gateway module...
|
You need to...
|
---|---|
Process Data page
|
Rebuild and transfer the Control Expert project file to the CPU, then transfer the HART gateway module DTM configuration to the CPU.
|
EtherNet/IP Configuration page
|
|
General Information page Device Name setting
|
Transfer the HART gateway module DTM configuration to the CPU.
|
SNMP Configuration page
|
|
Parameter Configuration page
|
|
Security page
|
Step
|
Action
|
---|---|
1
|
In the main menubar, select Build → Rebuild All Project. Control Expert builds the project. When the rebuild is complete, the task bar displays the word “Built”.
|
2
|
In the main menubar, select PLC → Set Address.... The Set Address dialog opens.
|
3
|
In the PLC area of the Set Address dialog:
Control Expert displays a message box if the connection is successful. Click OK.
|
4
|
In the main menubar, select PLC → Connect.
|
5
|
In the main menubar, select PLC → Transfer Project to PLC. The Transfer Project to PLC dialog opens.
|
6
|
Click Transfer. The project file is transferred to the CPU.
|
Step
|
Action
|
---|---|
1
|
Confirm that Control Expert remains connected to the CPU. If not, select PLC → Connect.
|
2
|
In the DTM Browser, select the HART gateway module DTM (for example, the BMEAHI0812).
|
3
|
Click the right mouse button, then navigate through several sub-menus to select the following command: Device menu → Additional functions → Transfer to FDR Server. Control Expert displays a message box indicating the transfer was successful.
|
4
|
Click OK.
|