HART Multiplexer Commands
Original instructions
Overview
The HART multiplexer within the HART analog I/O modules support the following HART multiplexer commands.
Universal Commands
Command
Description
1
Read primary variable
2
Read loop current and percentage of range
3
Read dynamic variables and loop current
6
Write polling address
7
Read loop configuration
8
Read dynamic variable classifications
9
Read device variables with status
11
Read unique identifier associated with tag
12
Read message
13
Read tag, descriptor, and date
14
Read primary variable transducer information
15
Read device information
16
Read final assembly number
17
Write message
18
Write tag, descriptor, and date
19
Write final assembly number
20
Read long tag
21
Read unique identifier associated with long tag
22
Write long tag
38
Reset configuration changed flag
48
Read additional device status
Common Practice Commands
Command
Description
42
Perform device reset
59
Write number of response preambles
106
Flush delayed response
ARCOM Multiplexer Common Practice Commands
Command
Description
128
Read parameters
129
Read loop status
130
Read instrument list from index
131
Read instrument static data
132
Write instrument static data
133
Remove instrument from instrument list
134
Read scan list from index
135
Read instrument dynamic data
136
Read instrument scan status
137
Write instrument scan status
138
Read instrument cumulative responses
139
Reset instrument cumulative responses
140
Read instrument tries and failures
141
Reset instrument tries and failures
142
Read counts of host communications
143
Reset counts of host communications
144
Read retry limits
145
Write retry limits
146
Read scan command
147
Write scan command
148
Read scan status
149
Write scan status
150
Read gender
151
Write gender
152
Read loop search type
153
Write loop search type
154
Rebuild loops
155
Copy command and reply (pass-through)