Parameter
|
Description
|
---|---|
Scan Command
|
Specify a scan command:
|
Scanning
|
Specify a scan mode:
|
Communication Retry Count
|
Type in the number of times the HART interface module resends a command to a non-responsive HART instrument. Valid values = 0...5. Default = 0.
|
Busy Retry Count
|
Type in the number of times the HART module resends a command after receiving a busy reply from a HART instrument. Valid values = 0...5. Default = 0.
|
Gender
|
The type of master:
|
Search Algorithm
|
Type of search performed for instruments on the loop:
|
Max Instruments Connected
|
The maximum number of instruments that can be connected to the multiplexer.
|
Instruments on Instrument List
|
The number of instruments on the instruments list.
|
State
|
Description
|
---|---|
Device Malfunction
|
A detected error rendered the instrument non-operational.
|
Configuration Changed
|
An operation occurred that changed the instrument configuration.
NOTE: Click Reset to clear detected faults and update module status. |
Cold Start
|
The instrument was reset, or power was cycled off then on.
|
More Status Available
|
Additional instrument information is available via HART command 48 (Read Additional Status Information).
|