Multiplexer Status
Original instructions
Multiplexer Scanning
Use the Multiplexer Status dialog to:
HART Port Parameters
The following HART port parameters can be accessed in the Multiplexer Status dialog:
Parameter
Description
Scan Command
Specify a scan command:
  • Read PV
  • Read Current (mA) and % of Range
  • Read Current (mA), PV, SV, TV and QV
Scanning
Specify a scan mode:
  • ON: enable scan
  • OFF: disable scan
Communication Retry Count
Type in the number of times the HART interface module resends a command to a non-responsive HART instrument. Valid values = 0...5. Default = 0.
Busy Retry Count
Type in the number of times the HART module resends a command after receiving a busy reply from a HART instrument. Valid values = 0...5. Default = 0.
Gender
The type of master:
  • Primary (default)
  • Secondary
Search Algorithm
Type of search performed for instruments on the loop:
  • Poll Address 0 Only
  • Poll Address 0 to 15 (default)
  • Poll Address 0 to 63
Max Instruments Connected
The maximum number of instruments that can be connected to the multiplexer.
Instruments on Instrument List
The number of instruments on the instruments list.
Multiplexer Status
The Multiplexer Status dialog indicates the status of the multiplexer as a whole, and monitors the existence or absence of several multiplexer states. The status of each state is indicated by the LED color, as follows:
The Multiplexer Status dialog displays the following multiplexer status states:
State
Description
Device Malfunction
A detected error rendered the instrument non-operational.
Configuration Changed
An operation occurred that changed the instrument configuration.
NOTE: Click Reset to clear detected faults and update module status.
Cold Start
The instrument was reset, or power was cycled off then on.
More Status Available
Additional instrument information is available via HART command 48 (Read Additional Status Information).