UNINTENDED EQUIPMENT OPERATION
Do not operate this equipment outside of its specified temperature range.
Failure to follow these instructions can result in injury or equipment damage.
|
Head module compatibility
|
|
|
Isolation:
|
|
1000 Vdc (1 minute duration)
|
|
1400 Vdc (1 minute duration)
|
|
|
1400 Vdc (1 minute duration)
|
|
Operating ambient temperature:
|
|
0...60 °C (32...140 °F)
|
|
-25...70 °C (-13...158 °F)
|
|
Vibration
|
10 mm / 3 g / x10 (per IEC60068-2-6)
|
|
Shock
|
30 g / 11 ms / x3 (per IEC60068-2-27)
|
|
Power consumption (3.3V)
|
400 mA
|
|
Power consumption (24V)
|
34 mA
|
|
Field device support
|
2-wire / 4-wire
|
|
Maximum overload authorized for inputs
|
|
|
Hot-swap support?
|
Yes
|
Number of channels
|
8
|
|
Type of inputs
|
High-density isolated fast inputs
|
|
Nominal range (full scale)
|
4-20 mA
|
|
Maximum conversion range
|
0.16...29.92 mA
|
|
Measurement accuracy for module:
|
|
0.15% of full scale(1)
|
|
0.3% of full scale(1)
|
|
|
0.55% of full scale(1)
|
|
Temperature drift
|
50 ppm / °C
|
|
Display resolution
|
15-bit plus sign bit
|
|
Least significant bit weight
|
0.458 μA
|
|
Refresh time:
|
|
4 ms(2)
|
|
4 ms(2)
|
|
Response time:
|
|
50 ms
|
|
4 ms
|
|
Input impedance
|
Internal conversion resistor (250 Ω) + Internal protection resistor (see note)
|
|
Detection type
|
broken wire
|
|
Monotonicity?
|
Yes
|
|
Common mode rejection (50/60 Hz)
|
80 dB
|
|
Crosstalk between channels DC and AC 50/60 Hz
|
> 80 dB
|
|
Non-linearity
|
0.02% of full scale
|
|
Repeatability at 25 °C of 10 minutes stabilization time
|
0.01% of full scale
|
|
Digital filtering
|
1st order
|
|
(1)Includes conversion resistor detected error. (2)Refresh times are for only the module internal buffer, and are impacted by PLC cycle time. |
HART protocols supported(2)
|
HART versions 5, 6 and 7
|
Number of channels
|
8
|
Scan time:
|
–
|
|
1 s
|
|
5 s
|
Detection time for a non-responsive device
|
= (scan time) + (timeouts)
|
HART command system
|
ARCOM (interface to a HART master)
|
Topology
|
Point-to-point
|
HART I/O mapping?
|
Yes
|
(1)Scan time is the same for each channel and for the module. The scan time depends on the byte length of the command. The scan time values do not include PLC cycle time, which should be added to determine overall scan time. (2)The eX80 HART input module supports HART up to versions 7.2 and 7.3. |