eX80 Analog I/O Module Diagnostics
Original instructions
LED Diagnostics
Use the combined states of the RUN, ERR, I/O, BS, An and Hn LEDs to diagnose the channel and module status for the BMEAHI0812 and BMEAHO0412 modules:
LED
Description
RUN
ERR
I/O
BS
A0...An
H0...Hn
OFF
OFF
OFF
OFF
All OFF
All OFF
Module has no power, or has stopped operating.
BLK green
BLK red
BLK red
BLK red & green
All OFF
All OFF
Module is performing self-test on power-up.
OFF
BLK red
OFF
X
All OFF
All OFF
The module is not yet configured, or is in the process of configuring its channels.
ON green
BLK red
X1
X
X
X
No communication between the output module and the head module.
NOTE: The module retains the previous I/O status.
ON green
OFF
OFF
X
ON green
X
Analog channel is operational.
ON green
OFF
OFF
X
OFF
X
Analog channel is disabled.
ON green
ON red
OFF
X
OFF
X
Analog to digital conversion detected error, or power supply detected error on channel.
ON green
OFF
ON red
X
FLK
X
Overflow or underflow error detected on channel.
ON green
OFF
ON red
X
BLK
X
Broken wired detected on input sensor channel or output actuator channel.
ON green
OFF
ON red
X
OFF
X
Calibration error detected on output channel.
ON green
OFF
ON red
X
X
ON red
No response from HART device on channel.
ON green
OFF
OFF
X
X
BS red
A HART device has been detected with a major difference from the device that is configured for the channel.
ON green
OFF
OFF
X
X
FLK red
A HART device has been detected with a minor difference from the device that is configured for the channel.
ON green
OFF
OFF
X
X
ON green
A HART device has been detected that is the same as the device configured for the channel, or a device with a detected major or minor difference has been accepted.
ON green
OFF
OFF
X
X
BLK green
The HART channel is connecting to a device.
ON green
OFF
OFF
X
X
OFF
HART communication disabled for the channel.
BLK green
OFF
OFF
BLK green
X
X
The I/O module is downloading firmware.
X
X
X
OFF
X
X
The module has not been assigned an IP address.
X
X
X
BLK green
X
X
The module has no established EIP Forward Open connections, but has an IP address.
X
X
X
ON green
X
X
The module has established an Ethernet connection.
X
X
X
BLK red
X
X
The module Ethernet connection has timed out. This is cleared only when the timed out connection is re-established or if the module is reset.
OFF
X
X
ON red
X
X
The module has detected that its IP address is already in use.
ON LED is steady on. OFF LED is off. FLK Flickering: ON for 50 ms, OFF for 50 ms, repeat. BLK Blinking: ON for 200 ms, OFF for 200 ms, repeat. BS Blinking Sequence: ON for 200 ms, OFF for 1,200 ms, repeat. X This LED is not used in determining the channel or module status.