Detailed Description of T_ANA_IN_GEN-type IODDT Objects
Original instructions
At a Glance
The tables below present the T_ANA_IN_GEN-type IODDT objects that are applicable to the BME AHI 0812, BMX AMI 0410, BMX AMI 0800 and BMX AMI 0810 input modules, to the inputs of the BMX AMM 600 mixed module and to the BMX ART 0414/0814 analog input module.
Input Measurement
The analog input measurement object is as follows.
Standard symbol
Type
Access
Meaning
Address
VALUE
INT
R
Analog input measurement.
%IWr.m.c.0
%Ir.m.c.ERR Error Bit
The %Ir.m.c.ERR error bit is as follows:
Standard symbol
Type
Access
Meaning
Address
CH_ERROR
BOOL
R
Detected error bit for analog channel.
%Ir.m.c.ERR