140 CPS 114 20 Specifications
Original instructions
General Specifications
Operating mode
Standalone
Summable
Internal power dissipation (electric losses)
11 W
Network power consumption
Electric losses + (5.1 x Iout)1
Power factor
0.5
1: Iout: sum of currents consumption by all modules in rack (in A)
140 CPS 114 20 power supplies are designed to not require the external EMI filter, ferrite bead and Olflex cable.
Input
Input voltage
93 ... 138 VAC
170 ... 264 VAC
Input frequency
47 ... 63 Hz
Input voltage total harmonic distortion
Less than 10% of the fundamental rms value
Input current
1.2 A @ 115 VAC
0.7 A @ 230 VAC
Inrush current
≤ 20 A @ 115 VAC
≤ 25 A @ 230 VAC
VA rating
160 VA @ 11 A
Fusing (external)
2.0 A slow-blow
Input power interruption
1/2 cycle @ full load and minimum rated line voltage / frequency. No less than 1 s between interruptions.
Output to Bus
Voltage
5.1 VDC
Max. current
Standalone
11 A @ 60 °C
Summable
a) Two 140 CPS 114 20(total load capacity)
20 A @ 60 °C
b) One 140 CPS 114 20 and one 140 CPS 114 10
16 A @ 60 °C
Min. current
not required
Protection
Over-current, Over-voltage