Operating mode
|
Standalone
|
Redundant
|
|
Internal power dissipation (electric losses)
|
11 W
|
Network power consumption
|
Electric losses + (5.1 x Iout)1
|
Power factor
|
0.5
|
1: Iout: sum of currents consumption by all modules in rack (in A)
|
Input voltage
|
93 ... 138 VAC
|
170 ... 263 VAC
|
|
Input frequency
|
47 ... 63 Hz
|
Input voltage total harmonic distortion
|
Less than 10% of the fundamental rms value
|
Input current
|
1.2 A @ 115 VAC
|
0.7 A @ 230 VAC
|
|
Inrush current
|
≤20 A @ 115 VAC
|
≤25 A @ 230 VAC
|
|
VA Rating
|
160 VA @ 11 A
|
Fusing (external)
|
2.0 A slow-blow
|
Input power interruption
|
1/2 cycle @ full load and minimum rated line voltage / frequency. No less than 1 s between interruptions.
|
Voltage
|
5.1 VDC
|
||
Max. Current
|
Standalone
|
11 A @ 60°C
|
|
Redundant
|
a) Two 140 CPS 124 20
|
10 A @ 60°C
|
|
b) Three 140 CPS 124 20
|
20 A @ 60°C
|
||
c) One 140 CPS 124 20 and one 140 CPS x24 00
|
6 A @ 60°C
|
||
9 A @ 40°C
|
|||
d) One 140 CPS 124 20 and two 140 CPS x24 00
|
12 A @ 60°C
|
||
18 A @ 40°C
|
|||
e) Two 140 CPS 124 20 and one 140 CPS x24 00
|
16 A @ 60°C
|
||
19 A @ 40°C
|
|||
140 CPS x24 00 means 140 CPS 224 00 or 140 CPS 424 00.
|
|||
Min. current
|
Not required
|
||
Protection
|
Over-current, over-voltage
|