Operating mode
|
Standalone
|
|
Redundant
|
|
|
Internal power dissipation (in W)
|
7 + (1.5 x Iout1)
|
|
Network power consumption
|
Electric losses + (5.1 x Iout)
|
|
1: Iout: sum of currents consumption by all modules in rack (in A)
|
|
|
Input voltage
|
20 ... 30 Vdc
|
|
Input current
|
3.8 A
|
|
Inrush current
|
25 A @ 24 Vdc
|
|
Input ripple
|
2.4 Vdc peak-to-peak, 94 ... 189 Hz
|
|
Input Power Interruption
|
1 ms max. @ 24 Vdc (without capacitor)
Hold-up capacitor timing chart (with a capacitor):
![]() |
|
Fusing (external)
|
5.0 A slow-blow
|
|
Voltage
|
5.1 Vdc
|
||
|
Max. Current
|
Standalone
|
Operating curve:
![]() |
8 A @ 40 °C (104 °F)
6 A @ 60 °C (140 °F)
|
|
Redundant
|
a) Two 140 CPS x24 00
|
8 A @ 40 °C (104 °F)
|
|
|
6 A @ 60 °C (140 °F)
|
|||
|
b) Three 140 CPS x24 00
|
16 A @ 40 °C (104 °F)
|
||
|
12 A @ 60 °C (140 °F)
|
|||
|
c) One 140 CPS 224 00 and one 140 CPS x24 00
|
8 A @ 40 °C (104 °F)
|
||
|
6 A @ 60 °C (140 °F)
|
|||
|
d) One 140 CPS 224 00 and two 140 CPS x24 00
|
16 A @ 40 °C (104 °F)
|
||
|
12 A @ 60 °C (140 °F)
|
|||
|
e) Two 140 CPS 224 00 and one 140 CPS x24 00
|
16 A @ 40 °C (104 °F)
|
||
|
12 A @ 60 °C (140 °F)
|
|||
|
140 CPS x24 00 means 140 CPS 224 00 or 140 CPS 424 00.
|
|||
|
Protection
|
Over-current, over-voltage
|
||
|
Surge withland
|
2.3 x max. rated input voltage for 1.3 ms
|
||