Operating mode
|
Standalone
|
Internal power dissipation (electric losses)
|
2 + (1.8 x Iout)
|
Network power consumption
|
Electric losses + (5.1 x Iout)1
|
1: Iout: sum of currents consumption by all modules in rack (in A)
|
Input voltage
|
20 ... 30 VDC
|
Input current
|
1.6 A
|
Inrush current
|
30 A
|
Fusing (external)
|
2.5 A slow-blow
|
Voltage
|
5.1 VDC
|
Max. current
|
3 A
|
Min. current
|
0.3 A
|
Protection
|
Over-current, over-voltage
|