140 CPS 114 10 Specifications
Original instructions
General Specifications
Operating mode
Standalone
Summable
Internal power dissipation (in W)
6.0 + 1.5 x IOUT (where IOUT is in A)
Input
Input voltage
93 ... 138 VAC
170 ... 276 VAC
Input frequency
47 ... 63 Hz
Input voltage total harmonic distortion
Less than 10% of the fundamental rms value
Input current
1.1 A @ 115 VAC
0.6 A @ 230 VAC
Inrush Current
38 A @ 115 VAC.
19 A @ 230 VAC
VA Rating
130 VA
Fusing (external)
2.0 A slow-blow recommended
Input Power Interruption
1/2 cycle @ full load and minimum rated line voltage / frequency. No less than 1 second between interruptions.
Output to Bus
Output to Bus
Voltage
5.1 VDC
Current
8 A @ 60 °C
min. Current not required
Protection
Over Current, Over Voltage