140 CPS 114 00 Specifications
Original instructions
General Specifications
Operating Mode
Standalone
Internal power dissipation (in Watts)
6.0 + 1.5 x IOUT (where IOUT is in A)
Input
Input voltage
93 ... 138 VAC
170 ... 276 VAC
Input frequency
47 ... 63 Hz
Input voltage total harmonic distortion
Less than 10% of the fundamental rms value
Input current
1.1 A @ 115 VAC
0.6 A @ 230 VAC
Inrush current
38 A @ 115 VAC
19 A @ 230 VAC
VA rating
130 VA
Fusing (external)
2.0 A slow-blow
Input power interruption
1/2 cycle @ full load and minimum rated line voltage / frequency. No less than 1 s between interruptions.
Output to Bus
Voltage
5.1 VDC
Current
8 A @ 60 °C (see the operating curve)
min. current not required
Operating Curve:
Protection
Over-current, over-voltage