Process power supply modules/units
|
TBX SUP 10
|
TBX SUP 1011/1021
TSX SUP 1051/1101
|
|
---|---|---|---|
Connection to screw terminal blocks
max. capacity per terminal
|
mm2
|
1 terminal per output
1 x 2.5
|
1011/1021/1051/A02:1 output terminal
1101 : terminals/output
2x1.5 with end or 1x2.5
|
Temperature:
Storage
Operation
|
°C
°C
|
-25 to +70
+5 to +55
|
-25 to +70
0 to +60 (TSX SUP 1011/1021/1051/1101
|
Relative humidity
|
%
|
5-95
|
|
Cooling
|
%
|
By natural convection
|
|
User safety
|
-
|
TBTS (EN 60950 and IEC1131-2)
|
|
Dielectric resistance:
Primary/secondary
Primary/ground
Secondary/ground
|
V rms
V rms
V rms
|
50/60Hz-1 mm
1500
1500
500
|
3500
2200
500
|
Insulation resistance
Primary/secondary
Primary/ground
|
Mega Ohms
Mega Ohms
|
>=100
>=100
|
|
Leakage Current
|
I<=3.5 mA (EN 60950)
|
||
Electrostatic discharge
immunities
|
6 kV contact/8 kV air
(IEC 1000-4-2 compliant)
|
||
Fast electric transient
|
2 kV (series mode and common mode on input and output)
|
||
Electromagnetic
field influence
|
10 V/m, 80MHz to 1 GHz
|
||
Rejected electromagnetic disturbances
|
(compliant with FCC 15-A and EN 55022 class A)
Test conditions: nominal U and I, resistive load,
cable: 1 meter horizontal, 0.8 meter vertical
|
||
Shock wave
|
Input: 4kV MC, 2kV MS Outputs: 2kV MF, 0.5 kV MS
(IEC 1000-4-5 compliant)
|
||
Vibration (1)
|
1 mm 3 Hz to 13.2 Hz 1g 57 Hz to 150 Hz
(IEC 68-2-6 compliant, FC test)
|
||
Level of protection
|
IP 20.5
|
IP 20.5, terminal block IP 21.5
|
|
MTBF at 40°C
Service life at 50°C
|
H
|
100 000
|
|
H
|
30,000 (at nominal voltage and at 80% of nominal power)
|