Environmental characteristics
(Original Document)
Table of characteristics
The following table gives the electrical characteristics of the power supplies: TBX SUP 10 and TSX SUP 10x:
Process power supply modules/units
TBX SUP 10
TBX SUP 1011/1021
TSX SUP 1051/1101
Connection to screw terminal blocks
max. capacity per terminal
mm2
1 terminal per output
1 x 2.5
1011/1021/1051/A02:1 output terminal
1101 : terminals/output
2x1.5 with end or 1x2.5
Temperature:
Storage
Operation
°C
°C
-25 to +70
+5 to +55
-25 to +70
0 to +60 (TSX SUP 1011/1021/1051/1101
Relative humidity
%
5-95
Cooling
%
By natural convection
User safety
-
TBTS (EN 60950 and IEC1131-2)
Dielectric resistance:
Primary/secondary
Primary/ground
Secondary/ground
V rms
V rms
V rms
50/60Hz-1 mm
1500
1500
500
3500
2200
500
Insulation resistance
Primary/secondary
Primary/ground
Mega Ohms
Mega Ohms
>=100
>=100
Leakage Current
I<=3.5 mA (EN 60950)
Electrostatic discharge
immunities
6 kV contact/8 kV air
(IEC 1000-4-2 compliant)
Fast electric transient
2 kV (series mode and common mode on input and output)
Electromagnetic
field influence
10 V/m, 80MHz to 1 GHz
Rejected electromagnetic disturbances
(compliant with FCC 15-A and EN 55022 class A)
Test conditions: nominal U and I, resistive load,
cable: 1 meter horizontal, 0.8 meter vertical
Shock wave
Input: 4kV MC, 2kV MS Outputs: 2kV MF, 0.5 kV MS
(IEC 1000-4-5 compliant)
Vibration (1)
1 mm 3 Hz to 13.2 Hz 1g 57 Hz to 150 Hz
(IEC 68-2-6 compliant, FC test)
Level of protection
IP 20.5
IP 20.5, terminal block IP 21.5
MTBF at 40°C
Service life at 50°C
H
100 000
H
30,000 (at nominal voltage and at 80% of nominal power)
(1) compliant with IEC 68-2-6, FC test with grid- or plate-mounted module or unit.