Electrical characteristics of process supply modules: TBX SUP 10 and TSX SUP 1011
|
|
(Original Document)
|
Process supply
|
TBX SUP 10 24V/1A
|
TSX SUP 1011 24V/1A
|
||
---|---|---|---|---|
![]() |
![]() |
|||
Primary
|
||||
Nominal input voltage
|
V
|
alternating 100240
direct 125
|
alternating 100240
direct 125
|
|
Input limit voltage
|
V
|
alternating 90264
direct 88156
|
alternating 85264
direct 105156
|
|
Network frequency
|
Hz
|
47...63
|
47...63/360...440
|
|
Nominal input current (U=100V)
|
On
|
0.4
|
0.4
|
|
Maximum call current (1)
|
to 100 V
|
On
|
3
|
37
|
to 240 V
|
On
|
30
|
75
|
|
Maximum It on trigger (1)
|
to 100 V
|
As
|
0.03
|
0.034
|
to 240 V
|
As
|
0.07
|
0.067
|
|
Maximum I2t on trigger (1)
|
to 100 V
|
A2s
|
2
|
0.63
|
to 240 V
|
A2s
|
2
|
2.6
|
|
Power factor
|
0.6
|
0.6
|
||
Harmonic (3)
|
10% (Phi=0°and 180°)
|
10% (Phi=0°and 180°)
|
||
Full load efficiency
|
%
|
>75
|
>75
|
|
Secondary
|
||||
Output (2)
|
W
|
24
|
26(30)
|
|
Nominal output current (2)
|
On
|
1
|
1.1
|
|
Output voltage/accuracy at 25°C
|
V
|
24+/-5%
|
24+/-3%
|
|
Residual ripple (peak to peak)
Maximum HF noise (peak to peak)
|
mV
mV
|
240
240
|
150
240
|
|
Accepted length of micro-power outages (3)
|
ms
|
≤10 in AC
≤1 in DC
|
≤10 in AC
≤1 in DC
|
|
Protection against
|
Short circuits and overloads
|
continuous automatic reset
|
fallback to 0 and automatic reset after fault has disappeared
|
|
Over-voltages
|
V
|
cuts off at U>36
|
cuts off at U>36
|
|
Parallelization
|
no
|
yes with power optimization
|
||
Serialization
|
no
|
yes
|
||
Power dissipation
|
8
|
18
|