Introduction
The M580 Hot Standby system continuously monitors the system state, and adds to its diagnostic buffer an entry for each detected error or change of state event. You can view and handle this collection of events using the following tools:
web page, for events relating to the selected CPU.
Control Expert, for detected events relating to the Hot Standby system.
in
M580 Hot Standby System Messages
Each detected system event presents:
A message describing the event type.
An explanatory text symbol entry, more particularly describing the event.
A numeric decimal identifier, representing the combination of message and symbol.
The M580 Hot Standby system can display the following messages
ID (dec) |
Message (Event Text) |
Symbol (Event Type) |
Possible Cause |
---|---|---|---|
14101 |
Switch from Wait to Primary |
No Error |
– |
14102 |
Switch From Wait to Standby |
Linked to Primary. No Error |
– |
14103 |
Switch from Standby to Primary |
No remote PLC connection |
No Hot Standby link and EIO link between CPUs. |
14104 |
Switch from Standby to Primary |
Remote PLC not Primary |
|
14105 |
Switch from Standby to Wait |
Hsby Link Error |
|
14106 |
Switch from Standby to Stop |
PLC not in RUN |
Standby CPU stopped. |
14107 |
Switch from Primary to Wait |
Loc RIO err and no peer RIO err |
Former primary CPU lost connection to all (e)X80 EIO adapter modules; former standby (now primary) CPU maintains connection to at least one (e)X80 EIO adapter module. |
14108 |
Switch from Primary to Wait |
Swap Command |
Former primary CPU received swap command. |
14109 |
Switch from Primary to Stop |
PLC not in RUN |
Former primary CPU stopped (PAC in STOP or one task in HALT) |
14110 |
Switch from Primary to Wait |
PLC_B linked to Primary |
– |
14111 |
Peer PLC disconnection on RIO Link |
RIO Link Error |
Two breaks in Ethernet RIO cable have isolated the remote CPU. |
14112 |
Peer PLC disconnection on Hsby Link |
Hsby Link Error |
|
14113 |
Mismatch Error |
FW mismatch |
Different firmware versions in each CPU. |
14114 |
Mismatch Error |
Logic mismatch |
Different application logic revisions running in each CPU. |
14115 |
Mismatch Error |
Application mismatch |
Different applications running in each CPU. |
14116 |
Degraded Hsby Data transfer |
Data Layout mismatch |
Online changes to data structure have been made to primary CPU, but not transferred to standby. |
14117 |
Bad peer rotary switch config |
Not in a PLC_A and PLC_B config |
Rotary switch settings do not specify an A and a B PAC. |
14118 |
Power supply error |
Loss of redundancy |
One of the BMXCPS4002 redundant power supply units is no longer functioning. |