Introduction
On the Control Expert page, you can select a (PC) from a pull-down menu.
The Control Expert DTM installed.
(PC) menu is a list of IP addresses that are configured for a PC that has theTo make the connection, choose a CPU and the device network.
(PC) that is in the same network as theYou can execute these tasks through this connection:
Perform fieldbus discovery.
Execute Online Actions.
Send an explicit message to an EtherNet/IP device.
Send an explicit message to a Modbus TCP device.
Diagnose modules.
Open the Page
View the
for the CPU:Step |
Action |
---|---|
1 |
Open a Control Expert project that includes a M580 CPU. |
2 |
Open the ( ). |
3 |
In the CPU. , find the name that you assigned to the |
4 |
Double-click (or right-click CPU to open the configuration window. ) the name of the |
5 |
Select in the navigation pane. |
Property Descriptions
This table describes the parameters for the
:Field |
Parameter |
Description |
---|---|---|
Source Address |
Source IP Address (PC) |
A list of IP addresses assigned to network interface cards installed on your PC. NOTE: If the configured main IP address of the CPU is not in the subnet of any of the IP configured on the interface
cards of the PC, then the first interface
card IP is suggested by default.
|
Sub-Network Mask (read-only) |
The subnet mask that is associated with the selected source IP address (PC). |
|
EtherNet/IP Network Detection |
Begin detection range address |
The first IP address in the address range for automatic field bus discovery of EtherNet/IP devices. |
End detection range address |
The last IP address in the address range for automatic field bus discovery of EtherNet/IP devices. |
|
Modbus Network Detection |
Begin detection range address |
The first IP address in the address range for automatic field bus discovery of Modbus TCP devices. |
End detection range address |
The last IP address in the address range for automatic field bus discovery of Modbus TCP devices. |
Make the Connection
Connect to the
(PC):Step |
Action |
---|---|
1 |
Select an IP address from the (PC) pull-down menu. |
2 |
Press the button. |
3 |
In the CPU. , find the name that you assigned to the |
4 |
Right-click the name of the CPU and scroll to . |
TCP/IP Monitoring
Expand (+) the
heading in the configuration tree and select the item at level 1.The read-only information on this page monitors the IP parameters that were configured in Control Expert.
Managing Source IP Addresses for Mulitple PCs
When you connect a PC to a DTM-based Control Expert application, Control Expert requires that you define the IP address of the PC connected to the PLC, which is referred to as the source IP address (PC). Rather than having to perform a in Control Expert each time you connect a PC to the PLC, the source IP address (PC) is selected automatically when you import the Control Expert application. During application import, the DTM retrieves all available configured NIC addresses of a connected PC and matches the subnet mask of the master with the available NIC list.
If a match between the subnet mask of the master and the NIC list exists, Control Expert automatically selects the matched IP address as the source IP address (PC) in the page.
If multiple matches exist, Control Expert automatically selects the IP address nearest to the subnet mask.
If no match exists, Control Expert automatically selects the IP address to the nearest available subnet mask.