Operating temperature/hygrometry/altitude
Data table:
Ambient temperature when operative |
0°C to +60°C (IEC 1131-2 = +5°C to +55°C) |
Relative humidity |
10% to 95% (without condensation) |
Altitude |
0 to 2000 meters |
Power supply voltages
Data table:
Voltage |
nominal |
24 VDC |
48 VDC |
100 to 240VAC |
100...120/200...240 VAC |
limit |
19 to 30 VDC |
19...60VDC (1) |
90 to 264 VAC |
90 to 140/190 to 264VAC |
|
Frequency |
nominal |
- |
- |
50/60 Hz |
50/60 Hz |
limit |
- |
- |
47/63 Hz |
47/63 Hz |
|
Brown-outs |
duration |
≤ 1 μs |
≤ 1 μs |
≤ 1/2 period |
≤ 1/2 period |
repetition |
≥ 1 s |
≥ 1 s |
≥ 1 s |
≥ 1 s |
|
Harmonic rate |
|
- |
- |
10% |
10% |
Residual ripple included |
|
5% |
5% |
- |
- |
(1) Possible up to 34 VDC, limited to 1 hour every 24 hours.
For TSX PSY 1610 and TSX PSY 3610 power supplies, and when using relay output modules, this scope is reduced to 21.6V...26.4V.
Human and material safety
Data table:
Test Designation |
Norms |
Levels |
|
---|---|---|---|
Dielectric rigidity and Isolation resistance * |
IEC 61131-2 UL 508 CSA 22-2 N°142 IEC 60950 |
24 - 48 V Power supply 100 -220 V Power supply < 48V Discrete I/Os > 48V Discrete I/Os > 10 MΩ |
1500 Vrms 2000 Vrms 500 Vrms 2000 Vrms |
Maintaining ground connections* |
IEC 61131-2 UL 508 CSA 22-2 N°142 |
< 0.1 Ω / 30 A / 2 min |
|
Leakage Current * |
CSA 22-2 N°142 IEC 60950 |
< 3.5 mA fixed device |
|
Enclosures for protection * |
IEC 61131-2 CSA 22-2 N°142 IEC 60950 |
IP 20 |
|
Impact Resistance |
CSA 22-2 N°142 IEC 60950 |
Drop / 1.3 m / 500 g Sphere |
|
Legend |
|||
*: Tests required by EC directives |
Resistance of devices to power supply L.F. turbulence
Data table:
Test Designation |
Norms |
Levels |
---|---|---|
Voltage and frequency Variation * |
EN 50082-1 |
Un 15% / Nf 5% 30 min x 2 Un 20% / Nf 10% 5 s x 2 |
Continuous voltage variation * |
EN 50082-1 |
0.85 Un - 1.2 Un 30 + 30 min + 5% ripple maximum |
Harmonic 3 * |
IEC 61131-2 |
10% Un 0° / 5 min - 180° / 5 min |
Momentary Interruptions * |
IEC 61131-2 |
AC 10 ms DC 1 ms |
Voltage peaks and troughs * |
IEC 61131-2 |
Un-0-Un; Un / 60s 3 cycles separated by 10 s Un-0-Un; Un / 5s 3 cycles separated by 1 to 5 s Un-0.9-Un; Un / 60s 3 cycles separated by 1 to 5 s |
Legend |
||
Un: Nominal Voltage Nf: Nominal Frequency Ud: Power-on detection level |
||
*: Tests required by EC directives |
Resistance to H.F. turbulence
Data table:
Test Designation |
Norms |
Levels |
---|---|---|
Amortized oscillatory wave * |
IEC 61131-2 IEC 61000-4-12 |
AC / DC 1 kV SM 24 V Discrete I/Os 1 kV SM |
Fast transients (bursts) * |
EN 50082-1 IEC 61000-4-4 |
AC / DC Power Supply 2 kV WM / CM 48 V > Discrete I/Os 2 kV CM other ports 1 kV CM |
Hybrid shockwave |
IEC 61000-4-5 |
AC / DC Power Supply 2 kV WM / 1 kV SM AC Discrete I/Os 2 kV WM / 1 kV SM DC Discrete I/Os 2 kV WM / 0.5 kV SM Shielded Cable 1 kV CM |
Electrostatic Discharge * |
IEC 61131-2 IEC 61000-4-2 |
6 kV contact 8 kV air |
Electromagnetic Field * |
EN 50082-2 IEC 61000-4-3 |
10 V/m, 80MHz - 2 GHz Sinusoidal modulation amplitude 80% / 1kHz |
Conduit Turbulence * |
EN 50082-2 IEC 61000-4-6 |
10 V 0.15 MHz - 80 MHz Sinusoidal modulation amplitude 80% / 1kHz |
Legend |
||
SM: Serial mode CM: Common Mode WM: Wire Mode |
||
*: Tests required by EC directives |
Electromagnetic Emissions
Data table:
Test Designation |
Norms |
Levels |
---|---|---|
Conduction Limits * |
EN55022/55011 EN50081-2 |
Class A 150 kHz - 500 kHz quasi-peak 79 dB mV average 66 dB mV 500 kHz -30 kHz quasi-peak 73 dB mV average 60 dB mV |
Emission Limits *(1) |
EN55022/55011 EN50081-2 |
Class A d = 10 m 30 kHz -230 kHz quasi-peak 30 dB mV/m 230 kHz -1 kHz quasi-peak 37 dB mV/m |
Legend |
||
(1) This test is carried out outside the casing, with the devices secured to a metallic grill and wired as shown in the TSX DG KBL• Manual. |
||
*: Tests required by EC directives |
Resistance to climatic variation
Data table:
Test Designation |
Norms |
Levels |
---|---|---|
Dry heat |
IEC60068-2-2 Bd |
60°C / 16h (E.O) 40°C / 16h (E.F) |
Cold |
IEC60068-2-1 Ad |
0°C / 16h |
Continuous humid heat |
IEC60068-2-30 Ca |
60°C / 93% Hr /96h (E.O) 40°C / 93% Hr /96h (E.F) |
Cyclical humid heat |
IEC60068-2-30 Db |
(55°C E.O / 40°C E.F); - 25°C / 93-95% Hr 2 cycles: 12 o' clock - 12h o' clock |
Cyclical temperature variations |
IEC60068-2-14 Nb |
0°C; -60°C / 5 Cycles: 6 o'clock-6 o'clock (E.O.) 0°C; -40°C / 5 Cycles: 6 o'clock-6 o'clock (E.F) |
Temperature Rise |
IEC61131-2 UL508 CSA22-2 N°142 |
Ambient temperature: 60°C |
Legend |
||
E.O: Device open E.F: Device closed Hr: Relative Humidity |
Resistance to mechanical constraints
Data table:
Test Designation |
Standards |
Levels |
---|---|---|
Sinusoidal vibrations |
IEC60068-2-6 Fc |
3 Hz - 100 Hz / 1 mm amplitude / 0.7 Gn Endurance: rf / 90 min / axis (Q limit) < 10 3 Hz - 150 Hz / 1.5 mm / 2 Gn Endurance: 10 cycles (1 octave / min) |
Half-sinus shocks |
IEC60068-2-27 Ea |
15 Gn x 11 ms 3 shocks / direct. / axis |
Legend |
||
rf: Resonance Frequency Q: Amplification Coefficient |
Resistance to climatic variation
Data table:
Test Designation |
Standards |
Levels |
---|---|---|
Dry heat whilst inoperative |
IEC60068-2-2 Bb |
70°C / 96h |
Cold whilst inoperative |
IEC60068-2-1 Ab |
-25°C / 96h |
Humid heat whilst inoperative |
IEC60068-2-30 dB |
60°C; - 25°C / 93-95% Hr 2 cycles: 12 o' clock - 12h o' clock |
Thermal shocks whilst inoperative |
IEC60068-2-14 Na |
-25°C; -70°C / 2 Cycles: 3 o'clock - 3 o'clock |
Resistance to mechanical constraints
Data table:
Test Designation |
Standards |
Levels |
---|---|---|
Flat free drop |
IEC60068-2-32 Ed |
10 cm / 2 drops |
Free drop from controlled position |
IEC60068-2-31 Ec |
30° or 10 cm / 2 drops |
Random free drop (conditioned material) |
IEC60068-2-32 Method 1 |
1 m / 5 drops |