Operating temperature/hygrometry/altitude

Data table:

Ambient temperature when operative

0°C to +60°C (IEC 1131-2 = +5°C to +55°C)

Relative humidity

10% to 95% (without condensation)

Altitude

0 to 2000 meters

Power supply voltages

Data table:

Voltage

nominal

24 VDC

48 VDC

100 to 240VAC

100...120/200...240 VAC

limit

19 to 30 VDC

19...60VDC (1)

90 to 264 VAC

90 to 140/190 to 264VAC

Frequency

nominal

-

-

50/60 Hz

50/60 Hz

limit

-

-

47/63 Hz

47/63 Hz

Brown-outs

duration

≤ 1 μs

≤ 1 μs

≤ 1/2 period

≤ 1/2 period

repetition

≥ 1 s

≥ 1 s

≥ 1 s

≥ 1 s

Harmonic rate

-

-

10%

10%

Residual ripple included

5%

5%

-

-

(1) Possible up to 34 VDC, limited to 1 hour every 24 hours.

For TSX PSY 1610 and TSX PSY 3610 power supplies, and when using relay output modules, this scope is reduced to 21.6V...26.4V.

Human and material safety

Data table:

Test Designation

Norms

Levels

 

Dielectric rigidity and Isolation resistance *

IEC 61131-2

UL 508

CSA 22-2 N°142

IEC 60950

24 - 48 V Power supply

100 -220 V Power supply

< 48V Discrete I/Os

> 48V Discrete I/Os

> 10 MΩ

1500 Vrms

2000 Vrms

500 Vrms

2000 Vrms

Maintaining ground connections*

IEC 61131-2

UL 508

CSA 22-2 N°142

< 0.1 Ω / 30 A / 2 min

 

Leakage Current *

CSA 22-2 N°142

IEC 60950

< 3.5 mA fixed device

 

Enclosures for protection *

IEC 61131-2

CSA 22-2 N°142

IEC 60950

IP 20

 

Impact Resistance

CSA 22-2 N°142

IEC 60950

Drop / 1.3 m / 500 g Sphere

 
 

Legend

*: Tests required by EC directives

NOTE: The devices must be installed and wired according to the directions in the TSX DG KBL• manual.

Resistance of devices to power supply L.F. turbulence

Data table:

Test Designation

Norms

Levels

Voltage and frequency Variation *

EN 50082-1

Un 15% / Nf 5% 30 min x 2

Un 20% / Nf 10% 5 s x 2

Continuous voltage variation *

EN 50082-1

0.85 Un - 1.2 Un 30 + 30 min

+ 5% ripple maximum

Harmonic 3 *

IEC 61131-2

10% Un

0° / 5 min - 180° / 5 min

Momentary Interruptions *

IEC 61131-2

AC 10 ms

DC 1 ms

Voltage peaks and troughs *

IEC 61131-2

Un-0-Un; Un / 60s 3 cycles separated by 10 s

Un-0-Un; Un / 5s 3 cycles separated by 1 to 5 s

Un-0.9-Un; Un / 60s 3 cycles separated by 1 to 5 s

 

Legend

Un: Nominal Voltage Nf: Nominal Frequency Ud: Power-on detection level

*: Tests required by EC directives

NOTE: The devices must be installed and wired according to the directions in the TSX DG KBL• manual.

Resistance to H.F. turbulence

Data table:

Test Designation

Norms

Levels

Amortized oscillatory wave *

IEC 61131-2

IEC 61000-4-12

AC / DC 1 kV SM

24 V Discrete I/Os 1 kV SM

Fast transients (bursts) *

EN 50082-1

IEC 61000-4-4

AC / DC Power Supply 2 kV WM / CM

48 V > Discrete I/Os 2 kV CM

other ports 1 kV CM

Hybrid shockwave

IEC 61000-4-5

AC / DC Power Supply 2 kV WM / 1 kV SM

AC Discrete I/Os 2 kV WM / 1 kV SM

DC Discrete I/Os 2 kV WM / 0.5 kV SM

Shielded Cable 1 kV CM

Electrostatic Discharge *

IEC 61131-2

IEC 61000-4-2

6 kV contact

8 kV air

Electromagnetic Field *

EN 50082-2

IEC 61000-4-3

10 V/m, 80MHz - 2 GHz

Sinusoidal modulation amplitude 80% / 1kHz

Conduit Turbulence *

EN 50082-2

IEC 61000-4-6

10 V 0.15 MHz - 80 MHz

Sinusoidal modulation amplitude 80% / 1kHz

 

Legend

SM: Serial mode CM: Common Mode WM: Wire Mode

*: Tests required by EC directives

NOTE: The devices must be installed and wired according to the directions in the TSX DG KBL• manual.

Electromagnetic Emissions

Data table:

Test Designation

Norms

Levels

Conduction Limits *

EN55022/55011

EN50081-2

Class A

150 kHz - 500 kHz quasi-peak 79 dB mV

average 66 dB mV

500 kHz -30 kHz quasi-peak 73 dB mV

average 60 dB mV

Emission Limits *(1)

EN55022/55011

EN50081-2

Class A d = 10 m

30 kHz -230 kHz quasi-peak 30 dB mV/m

230 kHz -1 kHz quasi-peak 37 dB mV/m

 

Legend

(1) This test is carried out outside the casing, with the devices secured to a metallic grill and wired as shown in the TSX DG KBL• Manual.

*: Tests required by EC directives

NOTE: The devices must be installed and wired according to the directions in the TSX DG KBL• manual.

Resistance to climatic variation

Data table:

Test Designation

Norms

Levels

Dry heat

IEC60068-2-2 Bd

60°C / 16h (E.O)

40°C / 16h (E.F)

Cold

IEC60068-2-1 Ad

0°C / 16h

Continuous humid heat

IEC60068-2-30 Ca

60°C / 93% Hr /96h (E.O)

40°C / 93% Hr /96h (E.F)

Cyclical humid heat

IEC60068-2-30 Db

(55°C E.O / 40°C E.F); - 25°C / 93-95% Hr

2 cycles: 12 o' clock - 12h o' clock

Cyclical temperature variations

IEC60068-2-14 Nb

0°C; -60°C / 5 Cycles: 6 o'clock-6 o'clock (E.O.)

0°C; -40°C / 5 Cycles: 6 o'clock-6 o'clock (E.F)

Temperature Rise

IEC61131-2

UL508

CSA22-2 N°142

Ambient temperature: 60°C

 

Legend

E.O: Device open E.F: Device closed Hr: Relative Humidity

Resistance to mechanical constraints

Data table:

Test Designation

Standards

Levels

Sinusoidal vibrations

IEC60068-2-6 Fc

3 Hz - 100 Hz / 1 mm amplitude / 0.7 Gn

Endurance: rf / 90 min / axis (Q limit) < 10

3 Hz - 150 Hz / 1.5 mm / 2 Gn

Endurance: 10 cycles (1 octave / min)

Half-sinus shocks

IEC60068-2-27 Ea

15 Gn x 11 ms 3 shocks / direct. / axis

 

Legend

rf: Resonance Frequency Q: Amplification Coefficient

Resistance to climatic variation

Data table:

Test Designation

Standards

Levels

Dry heat whilst inoperative

IEC60068-2-2 Bb

70°C / 96h

Cold whilst inoperative

IEC60068-2-1 Ab

-25°C / 96h

Humid heat whilst inoperative

IEC60068-2-30 dB

60°C; - 25°C / 93-95% Hr

2 cycles: 12 o' clock - 12h o' clock

Thermal shocks whilst inoperative

IEC60068-2-14 Na

-25°C; -70°C / 2 Cycles: 3 o'clock - 3 o'clock

Resistance to mechanical constraints

Data table:

Test Designation

Standards

Levels

Flat free drop

IEC60068-2-32 Ed

10 cm / 2 drops

Free drop from controlled position

IEC60068-2-31 Ec

30° or 10 cm / 2 drops

Random free drop (conditioned material)

IEC60068-2-32 Method 1

1 m / 5 drops