CAUTION |
|
UNEXPECTED BEHAVIOR OF APPLICATION
Before using the BMXERT1604T/H module in an M340 configuration, check that the OS version of the PLC is 2.50 or later.
Failure to follow these instructions can result in injury or equipment damage.
|
|
Architecture
|
CPU Reference
|
Maximum Expert Channels/CPU
|
Maximum Number BMXERT1604T/H Modules/CPU
|
|---|---|---|---|
|
Local Architecture
|
BMX P34 1000
|
20
|
4
|
|
BMX P34 2000
|
36
|
8
|
|
|
BMX P34 2010
|
36
|
8
|
|
|
BMX P34 20102
|
36
|
8
|
|
|
BMX P34 2020
|
36
|
8
|
|
|
BMX P34 2030
|
36
|
9
|
|
|
BMX P34 20302
|
36
|
9
|
|
Module features and requirements
|
M580 local racks (Main and extended)
|
|||
|---|---|---|---|---|
|
BMXERT1604T/H
Time synchronization
|
|
Yes
|
Yes
|
|
|
No
|
Yes
|
||
|
Requirements
|
M580 CPU
|
Firmware version
|
All
|
Minimum V2.10
|
|
BMXERT1604T/H
|
Firmware version
|
All
|
Minimum V2.00
|
|
|
Control Expert Hardware Catalog device
|
BMX ERT 1604
|
BMX ERT 1604.2
|
||
|
Module features and requirements
|
X80 drop over M580 PAC (main and extended remote racks)
|
|||
|---|---|---|---|---|
|
BMXERT1604T/H
Time synchronization
|
|
Yes
|
Yes
|
|
|
No
|
Yes
|
||
|
Requirements
|
M580 CPU
|
Firmware version
|
Minimum V2.00(1)
|
Minimum V2.10
|
|
BMXERT1604T/H
|
Firmware version
|
All
|
Minimum V2.00
|
|
|
Control Expert Hardware Catalog device
|
BMX ERT 1604
|
BMX ERT 1604.2
|
||
|
BMXCRA31210
Drop end communicator
|
Firmware version
|
Minimum V2.00
|
Minimum V2.14
|
|
|
Control Expert Hardware Catalog device
|
BMXCRA31210 (SV>=2.00)
|
BMXCRA31210 (SV>=2.14)
|
||
|
Or
|
||||
|
BMECRA31210
Drop end communicator
|
Firmware version
|
Minimum V2.00
|
Minimum V2.14
|
|
|
Control Expert Hardware Catalog device
|
BMECRA31210 (SV>=2.00)
|
BMECRA31210 (SV>=2.10)
|
||
(1)For a M580 Hot Standby the minimum firmware is V2.10. |
||||
|
Module features and requirements
|
X80 drop over Quantum PLC (main and extended remote racks)
|
||
|---|---|---|---|
|
BMXERT1604T/H
Time synchronization
|
|
Yes
|
|
|
No
|
||
|
Requirements
|
BMXERT1604T/H
|
Firmware version
|
All
|
|
Control Expert Hardware Catalog device
|
BMX ERT 1604
|
||
|
BMXCRA31210(1)
Drop end communicator
|
Firmware version
|
Minimum V1.00
|
|
|
Control Expert Hardware Catalog device
|
BMXCRA31210 (SV>=1.00)
|
||
|
Or
|
|||
|
BMECRA31210(2)
Drop end communicator
|
Firmware version
|
Minimum V2.00
|
|
|
Control Expert Hardware Catalog device
|
BMECRA31210 (SV>=2.00)
|
||
(1)Requires a Quantum CPU with a firmware V3.10 or later (2)Requires a Quantum CPU with a firmware V3.20 or later |
|||
|
Architecture
|
CRA Reference
|
Maximum Expert Channels/CRA
|
Maximum Module Number/Drop (CRA)
|
Maximum Module Number/EIO Network
|
|---|---|---|---|---|
|
Remote I/O Architecture
|
BMXCRA31210
or
BMECRA31210
|
36
|
9
|
25
|