Specifications
Original instructions
RTD/Resistance Module Specifications
Specifications for the Quantum140 AII 330 00 module configured as an Intrinsically Safe RTD/Resistance input module are as follows.
Number of Channels
8 IN
RTD Types (Configurable)
Platinum (American and European) – PT100, PT200, PT500, PT1000
-200 °C to +850 °C
Nickel – N100, N200, N500, N1000
-60 °C to +180 °C
Measurement Current
PT100, PT200, N100, N200 PT500, PT1000, N500, N1000
2.5 mA 0.5 mA
Input Impedance
>10M ohms
Linearity
+/- 0.003% of full scale (0 ... 60°C)
Resolution
12 bits plus sign (0.1°C)
Absolute Accuracy
+/- 0.5 °C (25 °C) +/- 0.9 °C (0 .. 60 °C)
Accuracy Error @ 25°C
Typical: +/- 0.05% of full scale Maximum: +/- 0.1% of full scale
Isolation
Channel to Channel
None
Channel to Bus
> 100 dB @ 50/60 Hz
Input Filter
1780 VAC @ 47-63 Hz or 2500 VDC for 1 min.
Update Time (All Channels)
3-wire 2 or 4-wire
1.35 sec.
750 m sec.
Bus Current Required
400 mA
Power Dissipation
2 W
External Power
Not required for this module
Fault Detection
Out of range or broken wire conditions
Hot Swap
Not allowed per intrinsic safety standards
Fusing
Internal-not user accessible
Thermocouple/Millivolt Module Specifications
The following table shows the specifications for the Thermocouple/Millivolt module.
Number of Channels
8 IN
TC Types and Ranges
Types J K E T S R B
Ranges (°C) -210 ... +760
-270 ... +1370
-270 ... +1000
-270 ... +400
-50 ... +1665
-50 ... +1665
+130 ... +1820
Millivolt Ranges
-100 mV ... +100 mV*
-25 mV ... +25 mV*
*Open circuit detect can be disabled on these ranges
TC Circuit Resistance/Max Source Resistance
200 ohms max for rated accuracy
Input Impedance
>1M ohms
Input Filter
Single low pass @ nominal 20 Hz. Plus notch filter at 50/60 Hz
Normal Noise Rejection
120 dB min @ 50 or 60 Hz
Cold Junction Compensation (CJC)
Internal CJC operates 0 ... 60°C (errors are included in the accuracy specification). The connector door must be closed. Remote CJC can be implemented by connecting the TC (which monitors the external junction block temperature) to channel 1. Types J, K, and T are recommended for best accuracy.
Resolution
TC Ranges
Choice of: 1 degree C (Default) 0.1 degree C 1 degree F 0.1 degree F
Millivolt Ranges
+/- 100 mV range, 3.05 microvolts (16 bits)
+/- 25 mV range, 0.76 microvolts (16 bits)
TC Absolute Accuracy (see Note 1)
Types J, K, E, T (see Note 2)
+/- 2°C +/- 0.1% of reading
Types S, R, B (see Note 3)
+/- 4°C +/- 0.1% of reading
Millivolt Absolute Accuracy
@ 25°C
+/- 20 microvolts +/- 0.1% of reading
Accuracy Drift w/ Temperature
0.15 microvolts/°C + 0.0015% of reading/°C max.
Isolation
Channel to Channel
None
Channel to Bus
1780 VAC @ 47-63 Hz or 2500 VDC for 1 min.
Update Time
1 sec. (all channels)
Fault Detection
Out of range or broken wire conditions
Bus Current Required
400 mA
Power Dissipation
2 W
External Power
Not required for this module
Hot Swap
Not allowed per intrinsic safety standards
Fusing
Internal - not user accessible
NOTE: 1. Absolute accuracy includes all errors from the internal CJC, TC curvature, offset plus gain, for module temperature of 0 ... 60 degrees C. User supplied TC errors not included.
2. For type J and K, add 1.5 degrees C inaccuracy for temperatures below -100 degrees C.
Type B cannot be used below 130 degrees C.
4. All TC ranges have an open TC detect and upscale output. This results in a reading 7FFFh or 32767 decimal when an open TC is detected.