Specifications
Original instructions
General Specifications
General Specifications
Module Type
16 IN (2 groups x 8 points)
8 OUT (2 groups x 4 points)
External Power
Not required for this module
Power Dissipation
1.75 W + 0.36 x input points ON + 1.1 V x total outputs load Currents
Bus Current required (Module)
330 mA
I/O map
1 input word
0.5 output word
Fault Detection
Input: None
Output: Blown fuse detect, loss of field power.
Input Rating
Input Rating
ON level voltage
+15 ... +30 VDC
ON level current
2.0 mA (min.)
OFF leve voltage
+3 ... +5 VDC
OFF level current
0.5 mA (max.)
Internal Resistance
2.5 kohm
Absolute Maximum Input
Absolute Maximum Input
Continuous
30 VAC
1.3 ms
56 VAC decaying pulse
Voltage (Output)
Voltage (Output)
Operating Voltage (max.)
19.2 ... 30 VDC
Absolute Voltage (max.)
56 VDC for 1.3 ms decaying voltage pulse
ON State Drop / Point
0.4 VDC @ 0.5 A
Maximum Load Current
Maximum Load Current
Each Point
0.5 A
Each Group
2.0 A
Per Module
4 A
OFF State Leakage / Point
0.4 mA @ 30 VDC
Surge Current (max.)
Each Point: 5 A @ 500 ms duration (no more than 6 per minute)
Load Inductance / Capacitance (max.)
Load Inductance / Capacitance (max.)
Load Inductance (max.)
0.5 Henry @ 4 Hz switch frequency, or:
Load Capacitance (max.)
50 microF
Isolation
Isolation
Group to Group
500 VAC rms for 1 minute
Group to Bus
1780 VAC rms for 1 minute
Response (Input and Output)
Response (Input and Output)
OFF - ON
1 ms (max) - (resistive load output)
ON - OFF
1 ms (max) - (resistive load output)
Module Protection
Module Protection
Input Protection
Resistor limited
Output Protection
Transient Voltage Suppression (internal)