Specifications
Original instructions
General Specifications
General Specifications
Module Type
16 IN (2 groups x 8 points)
8 OUT (2 groups x 4 points)
External Power
85 ... 132 VAC required for output groups
Power Dissipation
5.5 W + 1.1 V x Total module load current
Bus Current required
250 mA
I/O map
1 input word
0.5 output word
Fault Detection
Input: None
Output: Blown fuse detect, loss of field power.
Operating Voltage and Input Current*
Operating Voltage and Input Current*
50 Hz
ON: 85 ... 132 VAC (11.1 mA max)
OFF: 0 ... 20 VAC
60 Hz
ON: 79 ... 132 VAC (13.2 mA max)
OFF: 0 ... 20 VAC
* Do not use outside the 47 ... 63 Hz range
Maximum Allowable Leakage Current from an External Device to be recognized as an OFF Condition.
2.1 mA
Typical Input Impedance
Typical Input Impedance
50 Hz
14.4 kohms capacitive
60 Hz
12 kohms capacitive
Absolute Maximum Input
Absolute Maximum Input
Continuous
132 VAC
10 s
156 VAC
1 Cycle
200 VAC
Response (Inputs)
Response (Inputs)
OFF - ON
Min: 4.9 ms. Max: 0.75 line cycle.
ON - OFF
Min: 7.3 ms. Max: 12.3 ms.
NOTE: Input signals must be sinusoidal with less than 6% THD and 63 Hz maximum frequency.
Maximum Voltage (Output)
Maximum Voltage (Output)
Continuous
85 ... 132 VDC
10 sec
156 VDC
1 Cycle
200 VDC
ON State Drop / Point
1.5 VDC
Maximum Load Current / OFF State Leakage
Maximum Load Current / OFF State Leakage
Each Point
4 A continuous
Each Group
4 A continuous
Per Module
8 A continuous (see chart below for derating above 50 degree)
OFF State Leakage / Point
2 mA @ 115 VDC
The following figure shows the 140 DAM 590 00 Operating Curve.
Maximum Surge Current / Min. Load Current
Maximum Surge Current / Min. Load Current
One Cycle
30 A per point, 45 A per group
Two Cycle
20 A per point, 30 A per group
Three Cycle
10 A per point, 25 A per group
Min. Load Current
5 mA
Response
Response
OFF - ON / ON - OFF
0.5 of one line cycle max.
Applied DV / DT
400 V / micro sec
Isolation
Isolation
Group to Group
1000 VAC for 1 minute
Input or Output to Bus
1780 VAC for 1 minute