Specifications
Original instructions
General Specifications
General Specifications
Module Type
16 OUT (normaly open)
External Power
Not required for this module
Power Dissipation
5.5 W + 0.5 W x input points ON
Bus Current required (Module)
1100 mA
I/O map
1 output word
Operating Voltage
Operating Voltage
AC
20 ... 250 VAC
DC
5 ... 30 VDC
30 ... 150 VDC (reduced load Current)
Maximum Load Current
Maximum Load Current
Each Point
2 Amps per point maximum at 250 VAC, 30 VDC at 60 deg C ambient.
1 A Tungsten lamp load
1 A @ a power factor of 0.4
1/8 hp @ 125 / 250 VAC
Each Point (30 ... 150 VDC)
300 mA (restive load)
100 mA (L/R = 10 msec)
Surge Current (max.)
10 A capacitive load @ t = 10 ms
Minimum Load Current
Minimum Load Current
Each Point
50 mA
Note: Minimum load Current if the contact is used at rated loads of 5 ... 150 VDC or 20 ... 250 VDC
OFF State Leakage
< 100 μA
Isolation
Isolation
Output to Output
1780 VAC rms for one minute
Field to Bus
1780 VAC rms for one minute
2500 for one minute
Response
Response
OFF - ON
10 ms (max.)
ON - OFF
20 ms (max.)
Relay
Relay
Relay type
Form A
Contact Protection
Varistor 275 V (internal)
Mechanical Operations
10,000,000
Electrical Operations
200,000 (resistive load @ max. Voltage and Current)
Electrical Operations (30 ... 150 VDC) (see note below)
100,000 @ 300 mA (resistive load)
50,000 @ 500 mA (resistive load)
100,000 @ 100 mA (L/R = 10 msec)
100,000 Interposing Relay (Westinghouse Style 606B, Westinghouse type SG, Struthers Dunn 219 x 13 XP)
Switching Capability
500 VA (resistive load)
Fuses
Fuses
Internal
None
External
User installed per local and national electrical codes
NOTE: Relay contact life for inductive loads may be significantly increased by using external contact protection such as a clamping diode across the load.