Specifications
Original instructions
General Specifications
General Specifications
Module Type
96 OUT (6 groups x 16 points)
External Power
19.2 ... 30 VDC 19.2 A max. (determined by load)
Power Dissipation
7.0 W
Bus Current required (Module)
250 mA (max.)
I/O map
6 output word
Fault Detection
Group indication about loss of field power, short circuit or overload.
Voltage
Voltage
Operating Voltage (max.)
19.2 ... 30 VDC
ON State Drop / Point
0.5 VDC @ 0.5 A
Maximum Load Current / Surge Current
Maximum Load Current / Surge Current
Each Point
0.5 A
Each Group
3.2 A
Per Module
19.2 A
Surge Current (max.)
2 A each point (internally limited)
OFF State Leakage / Point
< 1 mA @ 24 VDC
Isolation / Protection
Isolation / Protection
Output to Bus
500 VAC rms for 1 minute
Output Protection (internal)
Thermal overload and short circuit
Response (Resistive Loads)
Response (Resistive Loads)
OFF - ON
< 1 ms
ON - OFF
< 1 ms
Load Inductance / Capacitance (max.)
Load Inductance / Capacitance (max.)
Load Inductance (max.)
0.5 Henry @ 4 Hz switch frequency, or:
Load Capacitance (max.)
50 μF
Fuses
Fuses
Internal
-
External
User installed per local and national electrical codes