Module Type
|
32 OUT (4 groups x 8 points)
|
Logic
|
True Low
|
External Power (Us)
|
4.5 ... 5.5 VDC continuous
|
Absolute Voltage (Us)
|
15 VDC for 1.3 ms decaying pulse
|
Power Dissipation
|
4 W
|
Supply Current
|
400 mA + Load Current per Point
|
Bus Current required (Module)
|
350 mA
|
I/O map
|
2 output word
|
Fault Detection
|
Output: Blown fuse detect, loss of field power.
|
ON level voltage
|
0.2 VDC (max.) @ 75 mA sinking
|
OFF level voltage
|
Vout = Us - 1.25 V @ 1 mA source
Vout = 3.2 V (min.) @ 1 mA, Us = 4.5 V
|
Internal Pullup Resistor
|
440 ohm
|
Each Point
|
75 mA (sinking)
|
Each Group
|
600 mA
|
Per Module
|
2.4 A
|
Surge Current (max.)
|
Each Point: 75 mA @ 500 ms duration (no more than 6 per minute)
|
Group to Group
|
500 VAC rms for 1 minute
|
Group to Bus
|
1780 VAC rms for 1 minute
|
Output Protection
|
Transient Voltage Suppression (internal)
|
OFF - ON
|
250 μs (max) - (resistive load)
|
ON - OFF
|
250 μs (max) - (resistive load)
|