Specifications
Original instructions
General Specifications
General Specifications
Module Type
32 IN (2 groups x 16 points)
External Power
+20 ... +30 VDC / 20 mA each group
Power Dissipation
7 W (all points on)
Bus Current required (Module)
250 mA
Operating Voltage and Current
Operating Voltage and Current
ON level current
2.5 mA (min.)
OFF level voltage
+5 VDC
OFF level current
min. 0.3 mA ... 1.2 mA
Response
Response
OFF - ON
2.2 ms
ON - OFF
3.3 ms
Isolation
Isolation
Group to Group
500 VAC rms for 1 minute
Group to Bus
1780 VAC rms for 1 minute
Open Circuit Monitoring
Open Circuit Monitoring
Broken wire detection
OFF Current < 0.15 mA
Shunt resistor
56 kohms recommended
Fuses
Fuses
Internal
None
External
User installed per local and national electrical codes