Module Type
|
32 IN (4 groups x 8 points)
|
External Power
|
Not required for this module
|
Power Dissipation
|
10.9 W (max)
|
Bus Current required
|
250 mA
|
I/O map
|
2 input words
|
Fault Detection
|
None
|
50 Hz
|
ON: 85 ... 132 VAC (11.1 mA max)
OFF: 0 ... 20 VAC
|
60 Hz
|
ON: 79 ... 132 VAC (13.2 mA max)
OFF: 0 ... 20 VAC
* Do not use outside the 47 ... 63 Hz range
|
Maximum Allowable Leakage Current from an External Device to be recognized as an OFF Condition.
|
2.1 mA
|
50 Hz
|
14.4 kohms capacitive
|
60 Hz
|
12 kohms capacitive
|
Group to Group
|
1780 VAC for 1 minute
|
Input to Bus
|
1780 VAC for 1 minute
|
Continuous
|
132 VAC
|
10 s
|
156 VAC
|
1 Cycle
|
200 VAC
|
OFF - ON
|
Min: 4.9 ms. Max: 0.75 line cycle.
|
ON - OFF
|
Min: 7.3 ms. Max: 12.3 ms.
|
Internal
|
None
|
External
|
User installed per local and national electrical codes
|